Key Specifications
:
EAN:4047621036939
UPC:804766688126
ETIM:5
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
EAN4047621036939
UPC804766688126
ETIM5
IDEA4
depth203 mm
width185 mm
UNSPSC15
eClass6
height306 mm
Group CodeR711
trip classCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
wire length
● minimum25.5 A
● upwards100 mm
Date5/3/2022Subject to change without notice© Copyright Siemens 2022
Metal FactorLAO-----
● PROFIBUSYes
● at 50 Hz110 ... 250 V
● at 60 Hz110 ... 250 V
● forwards10 mm
Product Group4981
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Quantity Unit1 Piece
● backwards0 mm
● downwards75 mm
Commodity Code85371098
Product family3RW52 soft starters
last modified:4/10/2022
service factor1
● CE markingYes
● Modbus RTUYes
● Modbus TCPYes
● auto-RESETYes
Net Weight (kg)5,200 Kg
● EtherNet/IPYes
● PROFIenergyYes; in connection with the PROFINET Standard communication module
● Soft TorqueYes
● UL approvalYes
● at the side5 mm
● of the fuse
● rated value200 ... 600 V
fastening methodscrew fixing
minimum load [%]15 %; Relative to smallest settable Ie
product categoryHybrid switching devices
product function
shock resistance15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
● CSA approvalYes
● manual RESETYes
● remote resetYes; By turning off the control supply voltage
Country of originCzech Republic
Marine / Shippingother
mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
operating voltage
product component
tightening torque
● analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
● error logbookYes; Only in conjunction with special accessories
LKZ_FDB/ CatalogIDCC-IC10
Packaging Quantity1
product brand nameSIRIUS
● pump ramp downYes
● torque controlNo
Function (EF000030)Single direction
Packaging Dimension303,00 x 403,00 x 336,00
Product DescriptionSIRIUS soft starter 200-600 V 63 A, 110-250 V AC Screw terminals Analog output
ambient temperature
degree of pollution3, acc. to IEC 60947-4-2
operational current
product designationSoft starter
● firmware updateYes
starting voltage [%]30 ... 100 %
stopping voltage [%]50 %; non-adjustable
vibration resistance15 mm to 6 Hz; 2g to 500 Hz
● HMI-High FeatureNo
● during operation-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
● PROFINET standardYes
digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)
environmental category
● of circuit breaker
Product Lifecycle (PLM)PM300:Active Product
With display (EF000458)-
● for control circuit100 ms
● not parameterizable2
EMC emitted interferenceacc. to IEC 60947-4-2: Class A
General Product ApprovalEMC
Release class (EF006668)Adjustable
adjustable motor current
number of analog outputs1
number of digital inputs1
product type designation3RW52
weight without packaging5.6 kg
● inside-delta circuitYes
Declaration of ConformityTest Certificates
Torque control (EF009215)false
number of digital outputs3
● at 40 °C rated value63 A
● at 50 °C rated value56 A
● at 60 °C rated value51 A
● ramp-down (soft stop)Yes
Export Control RegulationsAL : N / ECCN : N
Internal bypass (EF009214)true
certificate of suitability
● communication functionYes
Standard lead time ex-works100 Day/Days
Surcharge for Raw MaterialsNone
impulse voltage rated value6 kV
number of controlled phases3
tightening torque [lbf·in]
● at 40 °C after startup31 W
● at 50 °C after startup29 W
● at 60 °C after startup27 W
● ramp-up (soft starting)Yes
Package size unit of measureMM
UK Declaration of Conformity
control supply voltage at AC
● at 40 °C during startup882 W
● at 50 °C during startup744 W
● at 60 °C during startup659 W
● for main current circuit100 ms
Substance Prohibitance (Date)02/15/2018
electromagnetic compatibilityin accordance with IEC 60947-4-2
manufacturer's article number
type of electrical connection
● for control circuit solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● is supported HMI-StandardYes
● motor overload protectionYes; Electronic motor overload protection
● via software configurableYes
insulation voltage rated value600 V
width of connection bar maximum25 mm
● intrinsic device protectionYes
control supply voltage frequency50 ... 60 Hz
● at DC-13 at 24 V rated value1 A
● during storage and transport-40 ... +80 °C
● via software parameterizableNo
Operating frequency 1 rated value50 Hz
Operating frequency 2 rated value60 Hz
communication module is supported
● adjustable current limitationYes
● at AC-15 at 250 V rated value3 A
● is supported HMI-High FeatureYes
● of standard HMI module usable3RW5980-0HS00
operating power for 3-phase motors
start-up ramp time of soft starter0 ... 20 s
● at 230 V at 40 °C rated value18.5 kW
● at 400 V at 40 °C rated value30 kW
● at 500 V at 40 °C rated value37 kW
● at inside-delta circuit minimum44.2 A
Degree of protection (IP) (EF005474)IP00
design of the overvoltage protectionVaristor
surge voltage resistance rated value6 kV
● operating measured value displayYes; Only in conjunction with special accessories
Article Number (Market Facing Number)3RW5225-1AC15
Rated operating voltage Ue (EF002418)['200', '600']
Voltage type for actuating (EF008242)AC
current limiting value [%] adjustable130 ... 700 %
● of high feature HMI module usable3RW5980-0HF00
● of the gG fuse usable up to 690 V3NA3830-6; Type of coordination 1, Iq = 65 kA
Degree of protection (NEMA) (EF011959)-
WEEE (2012/19/EU) Take-Back ObligationYes
● at 200/208 V at 50 °C rated value15 hp
● at 220/230 V at 50 °C rated value20 hp
● at 460/480 V at 50 °C rated value40 hp
● at 575/600 V at 50 °C rated value50 hp
● between main and auxiliary circuit600 V
● of circuit breaker usable at 400 V3VA2163-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
● of circuit breaker usable at 500 V3VA2163-7MN32-0AA0; Type of coordination 1, Iq = 20 kA, CLASS 10
operating power [hp] for 3-phase motors
reference code according to IEC 81346-2Q
● at inside-delta circuit rated value200 ... 600 V
● at the digital inputs at AC maximum100 m
● of communication module Ethernet/IP3RW5980-0CE00
blocking voltage of the thyristor maximum1 800 V
● during storage according to IEC 607211K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
● between soft starter and motor maximum800 m
● removable terminal for control circuitYes
operational current at inside-delta circuit
required spacing with side-by-side mounting
● at AWG cables for control circuit solid1x (20 ... 12), 2x (20 ... 14)
● during operation according to IEC 607213K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
● during transport according to IEC 607212K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
● of communication module PROFIBUS usable3RW5980-0CP00
buffering time in the event of power failure
type of connectable conductor cross-sections
type of voltage of the control supply voltageAC
● evaluation of thermistor motor protectionNo
● of communication module Modbus RTU usable3RW5980-0CR00
● of communication module Modbus TCP usable3RW5980-0CT00
maximum permissible voltage for safe isolation
Integrated motor overload protection (EF007297)-
holding current in bypass operation rated value75 mA
switching capacity current of the relay outputs
utilization category according to IEC 60947-4-2AC 53a
● for main contacts with screw-type terminals4.5 ... 6 N·m
Rated control supply voltage Us at DC (EF003980)['-', '-']
power loss [W] at AC at current limitation 350 %
product feature integrated bypass contact systemYes
● at rotary coding switch on switch position 125.5 A
● at rotary coding switch on switch position 228 A
● at rotary coding switch on switch position 330.5 A
● at rotary coding switch on switch position 433 A
● at rotary coding switch on switch position 535.5 A
● at rotary coding switch on switch position 638 A
● at rotary coding switch on switch position 740.5 A
● at rotary coding switch on switch position 843 A
● at rotary coding switch on switch position 945.5 A
● at rotary coding switch on switch position 1048 A
● at rotary coding switch on switch position 1150.5 A
● at rotary coding switch on switch position 1253 A
● at rotary coding switch on switch position 1355.5 A
● at rotary coding switch on switch position 1458 A
● at rotary coding switch on switch position 1560.5 A
● at rotary coding switch on switch position 1663 A
Rated operation current Ie at 40 °C Tu (EF007039)63
control supply current in standby mode rated value30 mA
power loss [W] for rated value of the current at AC
Region Specific PriceGroup / Headquarter Price Group42S / 42S
contact rating of auxiliary contacts according to ULR300-B300
relative negative tolerance of the operating voltage-15 %
relative positive tolerance of the operating voltage10 %
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front with cover
● of communication module PROFINET standard usable3RW5980-0CS00
Rated control supply voltage Us at AC 50HZ (EF003978)['110', '250']
Rated control supply voltage Us at AC 60HZ (EF003979)['110', '250']
design of short-circuit protection for control circuit4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply
relative negative tolerance of the operating frequency-10 %
relative positive tolerance of the operating frequency10 %
installation altitude at height above sea level maximum5 000 m; Derating as of 1000 m, see catalog
locked-rotor current at close of bypass contact maximum2.5 A
protection class IP on the front according to IEC 60529IP00; IP20 with cover
— usable for High Faults at 460/480 V according to ULSiemens type: 3VA51, max. 125 A; Iq max = 65 kA
Rated surrounding temperature without derating (EF007074)40 °C
Rated power three-phase motor, inline, at 230 V (EF007053)18.5
Rated power three-phase motor, inline, at 400 V (EF007054)30.0
— usable for High Faults up to 575/600 V according to ULType: Class J / L, max. 225 A; Iq = 100 kA
● at 230 V at inside-delta circuit at 40 °C rated value30 kW
● at 400 V at inside-delta circuit at 40 °C rated value55 kW
● at 500 V at inside-delta circuit at 40 °C rated value55 kW
— usable for Standard Faults at 460/480 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 10 kA
— usable for Standard Faults at 575/600 V according to ULSiemens type: 3RV2742, max. 70 A or 3VA51, max. 125 A; Iq = 10 kA
● of the gG fuse usable at inside-delta circuit up to 500 V3NA3830-6; Type of coordination 1, Iq = 65 kA
— usable for Standard Faults up to 575/600 V according to ULType: Class RK5 / K5, max. 200 A; Iq = 10 kA
● at 200/208 V at inside-delta circuit at 50 °C rated value30 hp
● at 220/230 V at inside-delta circuit at 50 °C rated value30 hp
● at 460/480 V at inside-delta circuit at 50 °C rated value75 hp
● at 575/600 V at inside-delta circuit at 50 °C rated value75 hp
● of circuit breaker usable at 400 V at inside-delta circuit3VA2110-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
● of circuit breaker usable at 500 V at inside-delta circuit3VA2110-7MN32-0AA0; Type of coordination 1, Iq = 20 kA, CLASS 10
Rated power three-phase motor, inside delta, at 230 V (EF007055)30.0
Rated power three-phase motor, inside delta, at 400 V (EF007056)55.0
● for auxiliary and control contacts with screw-type terminals0.8 ... 1.2 N·m
● for control circuit finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
relative negative tolerance of the control supply voltage frequency-10 %
relative positive tolerance of the control supply voltage frequency10 %
inrush current peak at application of control supply voltage maximum12.2 A
Compliance with the substance restrictions according to RoHS directiveSince: 15.02.2018
● for main contacts for box terminal using both clamping points solid2x (2.5 ... 16 mm²)
REACH Art. 33 Duty to inform according to the current list of candidatesLead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-oneBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dibutylbis(pentane-2... CAS-No. 22673-19-4 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dibutylbis(pentane-2,4-dionato-O,O')tinBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dodecamethylcyclohex... CAS-No. 540-97-6 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dodecamethylcyclohexasiloxane (D6)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dodecachloropentacyclo[12... > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dodecachloropentacyclo[12.2.1.16,9.02,13.05,10]octadeca-7,15-diene (“Dechlorane Plus”™)covering any of its individual anti- and syn-isomers or any combination thereofBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
duration of inrush current peak at application of control supply voltage2.2 ms
relative negative tolerance of the control supply voltage at AC at 50 Hz-15 %
relative negative tolerance of the control supply voltage at AC at 60 Hz-15 %
relative positive tolerance of the control supply voltage at AC at 50 Hz10 %
relative positive tolerance of the control supply voltage at AC at 60 Hz10 %
● for inside-delta circuit at rotary coding switch on switch position 144.2 A
● for inside-delta circuit at rotary coding switch on switch position 248.5 A
● for inside-delta circuit at rotary coding switch on switch position 352.8 A
● for inside-delta circuit at rotary coding switch on switch position 457.2 A
● for inside-delta circuit at rotary coding switch on switch position 561.5 A
● for inside-delta circuit at rotary coding switch on switch position 665.8 A
● for inside-delta circuit at rotary coding switch on switch position 770.1 A
● for inside-delta circuit at rotary coding switch on switch position 874.5 A
● for inside-delta circuit at rotary coding switch on switch position 978.8 A
● for inside-delta circuit at rotary coding switch on switch position 1083.1 A
● for inside-delta circuit at rotary coding switch on switch position 1187.5 A
● for inside-delta circuit at rotary coding switch on switch position 1291.8 A
● for inside-delta circuit at rotary coding switch on switch position 1396.1 A
● for inside-delta circuit at rotary coding switch on switch position 14100 A
● for inside-delta circuit at rotary coding switch on switch position 15105 A
● for inside-delta circuit at rotary coding switch on switch position 16109 A
● for main contacts for box terminal using both clamping points stranded2x (6 ... 16 mm²), 2x (10 ... 50 mm²)
● for main contacts for box terminal using the back clamping point solid1x (2.5 ... 16 mm²)
● of back-up R fuse link for semiconductor protection usable up to 690 V3NE8024-1; Type of coordination 2, Iq = 65 kA
● for main contacts for box terminal using the front clamping point solid1x (2.5 ... 16 mm²)
relative negative tolerance of the operating voltage at inside-delta circuit-15 %
relative positive tolerance of the operating voltage at inside-delta circuit10 %
● for main contacts for box terminal using the back clamping point stranded1x (10 ... 70 mm²)
● of full range R fuse link for semiconductor protection usable up to 690 V3NE1022-0; Type of coordination 2, Iq = 65 kA
● for main contacts for box terminal using the front clamping point stranded1x (10 ... 70 mm²)
— usable for High Faults at 460/480 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 125 A; Iq max = 65 kA
— usable for High Faults at inside-delta circuit up to 575/600 V according to ULType: Class J / L, max. 225 A; Iq = 100 kA
● at AWG cables for main contacts for box terminal using the back clamping point1x (10 ... 2/0)
— usable for Standard Faults at 460/480 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 125 A; Iq = 10 kA
— usable for Standard Faults at 575/600 V at inside-delta circuit according to ULSiemens type: 3VA51, max. 125 A; Iq = 10 kA
● at AWG cables for main contacts for box terminal using the front clamping point1x (10 ... 2/0)
— usable for Standard Faults at inside-delta circuit up to 575/600 V according to ULType: Class RK5 / K5, max. 200 A; Iq = 10 kA
● for main contacts for box terminal using both clamping points finely stranded with core end processing2x (2.5 ... 35 mm²)
● for main contacts for box terminal using the back clamping point finely stranded with core end processing1x (2.5 ... 50 mm²)
● for main contacts for box terminal using the front clamping point finely stranded with core end processing1x (2.5 ... 50 mm²)
General Product ApprovalEMCConfirmationDeclaration of ConformityTest CertificatesMarine / ShippingUK Declaration of ConformityType Test Certificates/Test ReportMarine / ShippingotherConfirmationGeneral Product Approval

Product Description

SIRIUS soft starter 200-600 V 63 A, 110-250 V AC Screw connection Analog output
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top