| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4011209841567 |
| UPC | 662643922455 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 97 mm |
| width | 45 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 97 mm |
| B10 value | |
| Group Code | R711 |
| trip class | CLASS 10 |
| — upwards | 30 mm |
| ● at 24 V | 2 A |
| ● at 60 V | 0.15 A |
| ● at AC-3 | |
| Metal Factor | LAP----- |
| — forwards | 0 mm |
| ● at 120 V | 0.5 A |
| ● at 125 V | 0.5 A |
| ● at 230 V | 0.5 A |
| ● at 400 V | gL/gG 50 A |
| ● at 500 V | gL/gG 40 A |
| ● at 690 V | gL/gG 40 A |
| Date5/12/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 5332 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 30 mm |
| Commodity Code | 85362090 |
| Product family | SIRIUS 3RV2 motor starter protectors |
| last modified: | 1/27/2022 |
| Net Weight (kg) | 0,374 Kg |
| operating power | |
| — at the side | 9 mm |
| ● rated value | 690 V |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| product function | |
| required spacing | |
| Country of origin | Germany |
| Marine / Shipping | other |
| mounting position | any |
| operating voltage | |
| tightening torque | |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| failure rate [FIT] | |
| product brand name | SIRIUS |
| ● during storage | -50 ... +80 °C |
| Packaging Dimension | 49,00 x 102,00 x 102,00 |
| Product Description | Circuit breaker size S00 for transformer protection A-release 7...10 A N-release 208 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC |
| Vibration and Shock | Confirmation |
| ambient temperature | |
| operating frequency | |
| operational current | |
| product designation | Circuit breaker |
| ● at AC-3 maximum | 15 1/h |
| ● during operation | -20 ... +60 °C |
| ● during transport | -50 ... +80 °C |
| design of the product | For transformer protection |
| — solid or stranded | 2x (0,75 ... 2,5 mm²), 2x 4 mm² |
| ● for main contacts | |
| Product Lifecycle (PLM) | PM300:Active Product |
| design of the fuse link | |
| General Product Approval | Declaration of Conformity |
| Rated voltage (EF003977) | - |
| product type designation | 3RV2 |
| temperature compensation | -20 ... +60 °C |
| — at 230 V rated value | 2.2 kW |
| — at 400 V rated value | 4 kW |
| — at 500 V rated value | 5.5 kW |
| — at 690 V rated value | 7.5 kW |
| ● at 240 V rated value | 100 kA |
| ● at 400 V rated value | 100 kA |
| ● at 480 V rated value | 10 A |
| ● at 500 V rated value | 42 kA |
| ● at 600 V rated value | 10 A |
| ● at 690 V rated value | 4 kA |
| ● for 3-phase AC motor | |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | AL : N / ECCN : N |
| Number of poles (EF001391) | 3 |
| ● for auxiliary contacts | |
| ● ground fault detection | No |
| Standard lead time ex-works | 70 Day/Days |
| Surcharge for Raw Materials | None |
| design of screwdriver shaft | Diameter 5 to 6 mm |
| size of the circuit-breaker | S00 |
| size of the screwdriver tip | Pozidriv size 2 |
| ● for live parts at 400 V | |
| ● for live parts at 500 V | |
| ● for live parts at 690 V | |
| ● phase failure detection | Yes |
| Package size unit of measure | MM |
| — at 110/120 V rated value | 0.5 hp |
| — at 200/208 V rated value | 2 hp |
| — at 220/230 V rated value | 3 hp |
| — at 460/480 V rated value | 5 hp |
| — at 575/600 V rated value | 10 hp |
| ● for main current circuit | screw-type terminals |
| Substance Prohibitance (Date) | 10/01/2009 |
| type of electrical connection | |
| ● for single-phase AC motor | |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| design of the auxiliary switch | transverse |
| design of the overload release | thermal |
| ● at AC at 240 V rated value | 100 kA |
| ● at AC at 400 V rated value | 100 kA |
| ● at AC at 500 V rated value | 42 kA |
| ● at AC at 690 V rated value | 6 kA |
| Motor drive optional (EF007386) | false |
| operating frequency rated value | 50 ... 60 Hz |
| operational current rated value | 10 A |
| ● at AC-3 rated value maximum | 690 V |
| ● for grounded parts at 400 V | |
| ● for grounded parts at 500 V | |
| ● for grounded parts at 690 V | |
| design of the short-circuit trip | magnetic |
| proportion of dangerous failures | |
| ● at AC in hot operating state | 9.25 W |
| ● at AC-3 at 400 V rated value | 10 A |
| ● of the main contacts typical | 100 000 |
| Motor drive integrated (EF006697) | false |
| ● of auxiliary contacts typical | 100 000 |
| Type of control element (EF006976) | Toggle |
| product extension auxiliary switch | Yes |
| relative humidity during operation | 10 ... 95 % |
| yielded mechanical performance [hp] | |
| ● at AWG cables for main contacts | 2x (18 ... 14), 2x 12 |
| Degree of protection (IP) (EF005474) | IP20 |
| display version for switching status | Handle |
| surge voltage resistance rated value | 6 kV |
| Article Number (Market Facing Number) | 3RV2411-1JA15 |
| Rated permanent current Iu (EF001389) | 10.0 |
| With under voltage release (EF007518) | false |
| ● for auxiliary and control circuit | screw-type terminals |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| With switched-off indicator (EF007006) | false |
| ● between main and auxiliary circuit | 400 V |
| reference code according to IEC 81346-2 | Q |
| number of poles for main current circuit | 3 |
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
| product function short circuit protection | Yes |
| ● at AC in hot operating state per pole | 3.1 W |
| ● of the auxiliary and control contacts | M3 |
| mechanical service life (switching cycles) | |
| Overload release current setting (EF002336) | ['7', '10'] |
| Integrated earth fault protection (EF007296) | false |
| design of the thread of the connection screw | |
| full-load current (FLA) for 3-phase AC motor | |
| number of CO contacts for auxiliary contacts | 0 |
| number of NC contacts for auxiliary contacts | 1 |
| number of NO contacts for auxiliary contacts | 1 |
| shock resistance according to IEC 60068-2-27 | 25g / 11 ms |
| type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| power loss [W] for rated value of the current | |
| ● with low demand rate according to SN 31920 | 50 % |
| Complete device with protection unit (EF008906) | - |
| electrical endurance (switching cycles) typical | 100 000 |
| ● for main contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| ● with high demand rate according to SN 31920 | 5 000 |
| operational current of auxiliary contacts at AC-15 | |
| operational current of auxiliary contacts at DC-13 | |
| size of contactor can be combined company-specific | S00, S0 |
| DIN rail (top hat rail) mounting optional (EF008904) | - |
| Region Specific PriceGroup / Headquarter Price Group | 41E / 41E |
| contact rating of auxiliary contacts according to UL | C300 / R300 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| ● for auxiliary contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| breaking capacity maximum short-circuit current (Icu) | |
| installation altitude at height above sea level maximum | 2 000 m |
| protection class IP on the front according to IEC 60529 | IP20 |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | FALSE |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Position of connection for main current circuit (EF006671) | Other |
| Adjustment range undelayed short-circuit release (EF007131) | ['208', '208'] |
| arrangement of electrical connectors for main current circuit | Top and bottom |
| breaking capacity operating short-circuit current (Ics) at AC | |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| response value current of instantaneous short-circuit trip unit | 208 A |
| Number of auxiliary contacts as normally open contact (EF001376) | 1 |
| ● for short-circuit protection of the auxiliary switch required | Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) |
| Number of auxiliary contacts as normally closed contact (EF001377) | 1 |
| Adjustment range short-term delayed short-circuit release (EF007129) | ['-', '-'] |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) | 100.0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2009 |
| product component removable terminal for auxiliary and control circuit | No |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| adjustable current response value current of the current-dependent overload release | 7 ... 10 A |
| maximum permissible voltage for safe isolation in networks with grounded star point | |
| design of the fuse link for IT network for short-circuit protection of the main circuit | |
| General Product ApprovalDeclaration of ConformityConfirmationUK Declaration of ConformityDeclaration of ConformityTest CertificatesMarine / ShippingSpecial Test CertificateType Test Certificates/Test ReportMarine / ShippingotherConfirmationRailwayVibration and ShockConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide