Service time: Monday to Friday 9:00-18:00
3RV2042-4RB10 - 3RV2042-4RB10 SIEMENS Circuit breaker size S3 for motor protection, Class 20 A-release 65...84 A N-release 1..
In Stock Hot Product

3RV2042-4RB10

3RV2042-4RB10 SIEMENS Circuit breaker size S3 for motor protection, Class 20 A-release 65...84 A N-release 1..

$0.00USD
4510 in stock
Key Specifications
:Confirmation
EAN:4047621014272
UPC:804766759932
ETIM:5
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Confirmation
EAN4047621014272
UPC804766759932
ETIM5
IDEA4
depth176 mm
otherRailway
width70 mm
UNSPSC15
eClass6
height165 mm
B10 value
— solid2x (2.5 ... 16 mm²)
Group CodeR711
trip classCLASS 20
— upwards70 mm
● at AC-3
Metal FactorLDP-----
Date5/12/2022Subject to change without notice© Copyright Siemens 2022
Product Group3673
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Quantity Unit1 Piece
— downwards70 mm
Commodity Code85362090
Product familySIRIUS 3RV2 motor starter protectors
last modified:12/8/2021
Net Weight (kg)2,300 Kg
operating power
— at the side10 mm
● rated value690 V
Depth (EF000049)176.0
Width (EF000008)70.0
fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
product function
required spacing
Country of originGermany
Height (EF000040)165.0
Marine / Shippingother
mounting positionany
operating voltage
tightening torque
LKZ_FDB/ CatalogIDCC-IC10
Packaging Quantity1
product brand nameSIRIUS
● during storage-50 ... +80 °C
Packaging Dimension172,00 x 192,00 x 78,00
Product DescriptionCircuit breaker size S3 for motor protection, Class 20 A-release 65...84 A N-release 1170 A screw terminal Increased switching capacity 100 kA
ambient temperature
operating frequency
operational current
product designationCircuit breaker
● at AC-3 maximum15 1/h
● during operation-20 ... +60 °C
● during transport-50 ... +80 °C
design of the productFor motor protection
— solid or stranded2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
● for main contacts
Product Lifecycle (PLM)PM300:Active Product
product type designation3RV2
temperature compensation-20 ... +60 °C
— at 230 V rated value22 kW
— at 400 V rated value45 kW
— at 500 V rated value55 kW
— at 690 V rated value75 kW
● at 240 V rated value100 kA
● at 400 V rated value50 kA
● at 480 V rated value84 A
● at 500 V rated value5 kA
● at 600 V rated value84 A
● at 690 V rated value3 kA
● for 3-phase AC motor
Declaration of ConformityTest Certificates
Export Control RegulationsAL : N / ECCN : N
Number of poles (EF001391)3
● ground fault detectionNo
Standard lead time ex-works40 Day/Days
Surcharge for Raw MaterialsNone
size of the circuit-breakerS3
● for live parts at 400 V
● for live parts at 500 V
● for live parts at 690 V
● phase failure detectionYes
Package size unit of measureMM
UK Declaration of Conformity
— at 110/120 V rated value7.5 hp
— at 200/208 V rated value25 hp
— at 220/230 V rated value30 hp
— at 460/480 V rated value60 hp
— at 575/600 V rated value75 hp
● for main current circuitscrew-type terminals
Substance Prohibitance (Date)03/01/2017
type of electrical connection
● for single-phase AC motor
Device construction (EF008240)Built-in device fixed built-in technique
design of the overload releasethermal
● at AC at 240 V rated value100 kA
● at AC at 400 V rated value100 kA
● at AC at 500 V rated value10 kA
● at AC at 690 V rated value6 kA
Switch off technique (EF007007)Magnetic
operating frequency rated value50 ... 60 Hz
operational current rated value84 A
● at AC-3 rated value maximum690 V
● for grounded parts at 400 V
● for grounded parts at 500 V
● for grounded parts at 690 V
design of the short-circuit tripmagnetic
proportion of dangerous failures
● at AC in hot operating state34 W
● at AC-3 at 400 V rated value84 A
● of the main contacts typical25 000
● of auxiliary contacts typical25 000
Phase failure sensitive (EF007400)true
Rated operating voltage (EF001435)['690', '690']
Type of control element (EF006976)Turn button
With thermal protection (EF006233)thermal
product extension auxiliary switchYes
relative humidity during operation10 ... 95 %
yielded mechanical performance [hp]
Degree of protection (IP) (EF005474)IP20
display version for switching statusHandle
surge voltage resistance rated value8 kV
Article Number (Market Facing Number)3RV2042-4RB10
Rated permanent current Iu (EF001389)84.0
WEEE (2012/19/EU) Take-Back ObligationYes
● between main and auxiliary circuit400 V
reference code according to IEC 81346-2Q
number of poles for main current circuit3
● for main contacts for ring cable lug4.5 ... 6 N·m
product function short circuit protectionYes
● at AC in hot operating state per pole11.3 W
mechanical service life (switching cycles)
Overload release current setting (EF002336)['65', '84']
With integrated auxiliary switch (EF001387)false
full-load current (FLA) for 3-phase AC motor
shock resistance according to IEC 60068-2-2725g / 11 ms Sinus
type of connectable conductor cross-sections
— finely stranded with core end processing2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
power loss [W] for rated value of the current
● with low demand rate according to SN 3192050 %
Rated operation power at AC-3, 230 V (EF007025)22.0
Rated operation power at AC-3, 400 V (EF001364)45.0
electrical endurance (switching cycles) typical25 000
— finely stranded without core end processing2x (10 ... 35 mm²), 1x (10 ... 50 mm²)
● for main contacts with screw-type terminals4.5 ... 6 N·m
● with high demand rate according to SN 319205 000
With integrated under voltage release (EF001390)false
size of contactor can be combined company-specificS3
outer diameter of the usable ring cable lug maximum19 mm
Region Specific PriceGroup / Headquarter Price Group41E / 41E
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
breaking capacity maximum short-circuit current (Icu)
installation altitude at height above sea level maximum2 000 m
protection class IP on the front according to IEC 60529IP20
Type of electrical connection of main circuit (EF006819)Screw connection
Adjustment range undelayed short-circuit release (EF007131)['1170', '1170']
arrangement of electrical connectors for main current circuitTop and bottom
breaking capacity operating short-circuit current (Ics) at AC
insulation voltage with degree of pollution 3 at AC rated value1 000 V
response value current of instantaneous short-circuit trip unit1 170 A
Rated short-circuit breaking capacity lcu at 400 V, AC (EF007049)100.0
Compliance with the substance restrictions according to RoHS directiveSince: 01.03.2017
product component removable terminal for auxiliary and control circuitNo
REACH Art. 33 Duty to inform according to the current list of candidatesLead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
adjustable current response value current of the current-dependent overload release65 ... 84 A
maximum permissible voltage for safe isolation in networks with grounded star point
General Product ApprovalConfirmationKCDeclaration of ConformityTest CertificatesMarine / ShippingUK Declaration of ConformitySpecial Test CertificateType Test Certificates/Test ReportMarine / ShippingotherConfirmationotherRailwayConfirmationVibration and ShockGeneral Product Approval

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual