| Parameter | Value |
|---|---|
| Value | |
| EAN | 4047621001722 |
| UPC | 804766061646 |
| ETIM | 4 |
| IDEA | 4 |
| Depth | 149 mm |
| Width | 55 mm |
| other | Railway |
| Height | 140 mm |
| UNSPSC | 15 |
| eClass | 6 |
| B10 value | |
| Group Code | R711 |
| Trip class | CLASS 10 |
| Price Group | |
| — upwards | 50 mm |
| ● at AC-3 | |
| ● maximum | 2 000 m |
| ● typical | 20 000 |
| Confirmation | |
| Metal Factor | LBP----- |
| — forwards | 0 mm |
| ● at 240 V | none required |
| ● at 400 V | 160 |
| ● at 500 V | 125 |
| ● at 690 V | 100 |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| Product Group | 5334 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| — Backwards | 0 mm |
| — downwards | 50 mm |
| Commodity Code | 85362090 |
| Product family | SIRIUS 3RV2 motor starter protectors |
| last modified: | 08/13/2020 |
| Display version | |
| Net Weight (kg) | 1,207 Kg |
| Operating power | |
| — at the side | 10 mm |
| ● rated value | 690 V |
| Depth (EF000049) | 149.0 |
| Product function | |
| Required spacing | |
| Shock resistance | |
| Width (EF000008) | 55.0 |
| Country of origin | Germany |
| Height (EF000040) | 140.0 |
| Operating current | |
| Operating voltage | |
| Product extension | |
| Tightening torque | |
| Failure rate [FIT] | |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -50 ... +80 °C |
| Ambient temperature | |
| Operating frequency | |
| Packaging Dimension | 62,00 x 147,00 x 167,00 |
| Product Description | Circuit breaker size S2 for motor protection, CLASS 10 A-release 54...65 A N-release 845 A screw terminal Standard switching capacity with transverse auxiliary switches 1 NO+1 NC |
| Product designation | Circuit breaker |
| ● at AC-3 maximum | 15 1/h |
| ● Auxiliary switch | Yes |
| ● during operation | -20 ... +60 °C |
| ● during transport | -50 ... +80 °C |
| Design of the product | For motor protection |
| ● for main contacts | |
| ● mounting position | any |
| Response value current | |
| Design of the fuse link | |
| Product Lifecycle (PLM) | PM300:Active Product |
| General Product Approval | For use in hazardous locations |
| Product type designation | 3RV2 |
| Temperature compensation | -20 ... +60 °C |
| — at 230 V rated value | 18 500 W |
| — at 400 V rated value | 65 A |
| — at 500 V rated value | 45 000 W |
| — at 690 V rated value | 55 000 W |
| ● at 240 V rated value | 100 kA |
| ● at 400 V rated value | 30 kA |
| ● at 480 V rated value | 65 A |
| ● at 500 V rated value | 4 kA |
| ● at 600 V rated value | 62 A |
| ● at 690 V rated value | 2 kA |
| ● for switching status | Handle |
| Export Control Regulations | AL : N / ECCN : N |
| Number of poles (EF001391) | 3 |
| ● Ground fault detection | No |
| ● acc. to IEC 60068-2-27 | 25g / 11 ms Sinus |
| ● for auxiliary contacts | |
| Design of screwdriver shaft | Diameter 5 to 6 mm |
| Size of the circuit-breaker | S2 |
| Size of the screwdriver tip | Pozidriv 2 |
| Standard lead time ex-works | 1 Day/Days |
| Surcharge for Raw Materials | None |
| ● Phase failure detection | Yes |
| ● for live parts at 400 V | |
| ● for live parts at 500 V | |
| ● for live parts at 690 V | |
| Package size unit of measure | MM |
| — at 200/208 V rated value | 20 hp |
| — at 220/230 V rated value | 25 hp |
| — at 460/480 V rated value | 50 hp |
| — at 575/600 V rated value | 60 hp |
| — single or multi-stranded | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) |
| ● for three-phase AC motor | |
| Operating current rated value | 65 A |
| Design of the auxiliary switch | transverse |
| Design of the overload release | thermal |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| For use in hazardous locations | Declaration of Conformity |
| Product Dimensions (W x L x H) | Not available |
| ● at AC at 240 V rated value | 100 kA |
| ● at AC at 400 V rated value | 65 kA |
| ● at AC at 500 V rated value | 8 kA |
| ● at AC at 690 V rated value | 4 kA |
| Operating frequency rated value | 50 ... 60 Hz |
| Switch off technique (EF007007) | Magnetic |
| ● at AC-3 rated value maximum | 690 V |
| ● for grounded parts at 400 V | |
| ● for grounded parts at 500 V | |
| ● for grounded parts at 690 V | |
| Design of the short-circuit trip | magnetic |
| Proportion of dangerous failures | |
| ● at AC in hot operating state | 26 W |
| ● of the main contacts typical | 20 000 |
| ● of auxiliary contacts typical | 20 000 |
| Phase failure sensitive (EF007400) | true |
| Rated operating voltage (EF001435) | ['690', '690'] |
| Relative humidity during operation | 10 ... 95 % |
| Type of control element (EF006976) | Turn button |
| With thermal protection (EF006233) | thermal |
| Yielded mechanical performance [hp] | |
| Degree of protection (IP) (EF005474) | IP20 |
| Surge voltage resistance rated value | 6 kV |
| ● protection class IP on the front | IP20 |
| Article Number (Market Facing Number) | 3RV2031-4JA15 |
| Rated permanent current Iu (EF001389) | 65.0 |
| Reference code acc. to DIN EN 81346-2 | Q |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Electrical endurance (switching cycles) | |
| ● Protection class IP of the terminal | IP00 |
| ● at AWG conductors for main contacts | 2x (18 ... 2), 1x (18 ... 1) |
| Number of poles for main current circuit | 3 |
| Product function Short circuit protection | Yes |
| ● at AC in hot operating state per pole | 8.7 W |
| ● of the auxiliary and control contacts | M3 |
| ● with low demand rate acc. to SN 31920 | 50 % |
| Mechanical service life (switching cycles) | |
| ● with high demand rate acc. to SN 31920 | 5 000 |
| Overload release current setting (EF002336) | ['54', '65'] |
| With integrated auxiliary switch (EF001387) | true |
| Design of the thread of the connection screw | |
| Number of NC contacts for auxiliary contacts | 1 |
| Number of NO contacts for auxiliary contacts | 1 |
| Type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| ● at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
| ● of instantaneous short-circuit trip unit | 845 A |
| Power loss [W] for rated value of the current | |
| maximum permissible voltage for safe isolation | |
| Installation altitude at height above sea level | |
| Rated operation power at AC-3, 230 V (EF007025) | 18.5 |
| Rated operation power at AC-3, 400 V (EF001364) | 30.0 |
| ● for main contacts with screw-type terminals | 3 ... 4.5 N·m |
| Full-load current (FLA) for three-phase AC motor | |
| With integrated under voltage release (EF001390) | false |
| ● at 480 AC Y/277 V acc. to UL 489 rated value | 30 A |
| Size of contactor can be combined company-specific | S2 |
| Contact rating of auxiliary contacts according to UL | C300 / R300 |
| ● for auxiliary contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| Maximum short-circuit current breaking capacity (Icu) | |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| ● removable terminal for auxiliary and control circuit | No |
| Type of protection according to ATEX directive 2014/34/EU | Ex II (2) GD |
| ● Type of electrical connection for main current circuit | screw-type terminals |
| Adjustment range undelayed short-circuit release (EF007131) | ['845', '845'] |
| ● Operating current of auxiliary contacts at DC-13 at 60 V | 0.15 A |
| ● operating current of auxiliary contacts at AC-15 at 24 V | 2 A |
| ● operating current of auxiliary contacts at DC-13 at 24 V | 1 A |
| Arrangement of electrical connectors for main current circuit | Top and bottom |
| ● Operating current of auxiliary contacts at AC-15 at 230 V | 0.5 A |
| ● Operating current of auxiliary contacts at DC-13 at 110 V | 0 A |
| ● Operating current of auxiliary contacts at DC-13 at 220 V | 0 A |
| ● operating current of auxiliary contacts at DC-13 at 125 V | 0 A |
| Insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| Operational short-circuit current breaking capacity (Ics) at AC | |
| Certificate of suitability according to ATEX directive 2014/34/EU | DMT 02 ATEX F 001 |
| Rated short-circuit breaking capacity lcu at 400 V, AC (EF007049) | 65.0 |
| ● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A) |
| T1 value for proof test interval or service life acc. to IEC 61508 | 10 y |
| Compliance with the substance restrictions according to RoHS directive | Since: 10.04.2015 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| adjustable pick-up value current of the current-dependent overload release | 54 ... 65 A |
| ● Type of electrical connection for auxiliary and control current circuit | screw-type terminals |
| ● in networks with grounded star point between main and auxiliary circuit | 400 V |
| Design of the fuse link for IT network for short-circuit protection of the main circuit | |
| General Product ApprovalFor use in hazardous locationsKCFor use in hazardous locationsDeclaration of ConformityTest CertificatesMarine / ShippingMiscellaneousSpecial Test CertificateType Test Certificates/Test ReportMarine / ShippingotherRailwayConfirmationVibration and ShockConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide