| Parameter | Value |
|---|---|
| Value | |
| EAN | 4011209303867 |
| UPC | 754554412191 |
| Notes | Sucessor:Successor SIRIUS Innovations 3RU2 |
| depth | 118 mm |
| width | 55 mm |
| height | 105 mm |
| Group Code | R711 |
| trip class | CLASS 10 |
| Price Group | 41F |
| — upwards | 0 mm |
| ● at 24 V | 3 A |
| Metal Factor | L-O----- |
| — forwards | 0 mm |
| ● at 110 V | 3 A |
| ● at 120 V | 3 A |
| ● at 125 V | 3 A |
| ● at 220 V | 0.11 A |
| ● at 230 V | 2 A |
| ● at 400 V | 1 A |
| Product Group | 3707 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 0 mm |
| Commodity Code | 85364900 |
| Product family | Not available |
| last modified: | 08/27/2020 |
| Net Weight (kg) | 0,320 Kg |
| — at the side | 0 mm |
| required spacing | |
| ● on the front | IP20 |
| Country of origin | Germany |
| Marine / Shipping | other |
| ● mounting type | Contactor mounting |
| LKZ_FDB/ CatalogID | CC-IC10 |
| PLM Effective Date | Product is cancelled since: 01.10.2019 |
| Packaging Quantity | 1 |
| Type of protection | DMT 98 ATEX G 001 |
| product brand name | SIRIUS |
| ● for live parts | |
| Packaging Dimension | 61,00 x 96,00 x 111,00 |
| Product Description | Overload relay 40...50 A For motor protection Size S2, Class 10 Contactor mounting Main circuit: Screw terminal Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset !!! Phased-out product !!! Successor is SIRIUS 3RU2 Preferred successor type is >>3RU2136-4HD0<< |
| product designation | thermal overload relay |
| protection class IP | |
| ● shock resistance | 8g / 10 ms |
| ● mounting position | with vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back |
| Size of overload relay | S2 |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM410:Product cancellation |
| General Product Approval | For use in hazardous locations |
| Release class (EF006668) | CLASS 10 |
| Special Test Certificate | |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | ECCN : N / AL : N |
| Mounting method (EF000003) | - |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| ● for main current circuit | screw-type terminals |
| type of electrical connection | |
| Product Dimensions (W x L x H) | Not available |
| ● with side-by-side mounting | |
| Reset function input (EF011940) | - |
| relative humidity during operation | 100 % |
| Adjustable current range (EF008211) | ['40', '50'] |
| Reset function automatic (EF011941) | - |
| surge voltage resistance rated value | 6 kV |
| Article Number (Market Facing Number) | 3RU1136-4HD0 |
| Reset function push-button (EF011942) | - |
| reference code acc. to DIN EN 81346-2 | F |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ● ambient temperature during storage | -55 ... +80 °C |
| number of poles for main current circuit | 3 |
| ● ambient temperature during operation | -20 ... +70 °C |
| ● ambient temperature during transport | -55 ... +80 °C |
| Max. rated operation voltage Ue (EF007357) | 690 |
| ● for auxiliary and control current circuit | Cage Clamp terminals |
| operating current of auxiliary contacts at AC-15 | |
| operating current of auxiliary contacts at DC-13 | |
| ● number of CO contacts for auxiliary contacts | 0 |
| ● number of NC contacts for auxiliary contacts | 1 |
| ● number of NO contacts for auxiliary contacts | 1 |
| ● operating voltage at AC-3 rated value maximum | 690 V |
| size of contactor can be combined company-specific | S2 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| ● installation altitude at height above sea level maximum | 2 000 m |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| Number of auxiliary contacts as normally open contact (EF001376) | 1 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 1 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● type of connectable conductor cross-sections for main contacts solid | 2x (0.75 ... 16 mm²) |
| ● product function removable terminal for auxiliary and control circuit | No |
| adjustable pick-up value current of the current-dependent overload release | 40 ... 50 A |
| ● Type of connectable conductor cross-sections for main contacts stranded | 2x (0.75 ... 25 mm²), 0.75 ... 35 mm² |
| ● type of connectable conductor cross-sections for auxiliary contacts solid | 2x (0.5 ... 2.5 mm²) |
| ● power loss [W] for rated value of the current at AC in hot operating state | 15.6 W |
| ● type of connectable conductor cross-sections at AWG conductors for main contacts | 2x (18 ... 3), 1x (18 ... 1) |
| ● power loss [W] for rated value of the current at AC in hot operating state per pole | 5.2 W |
| ● design of the fuse link for short-circuit protection of the auxiliary switch required | fuse gL/gG: 6 A, quick: 10 A |
| ● type of connectable conductor cross-sections at AWG conductors for auxiliary contacts | 2x (20 ... 14) |
| ● type of connectable conductor cross-sections for main contacts finely stranded with core end processing | 2x (0.75 ... 16 mm²), 0.75 ... 25 mm² |
| ● type of connectable conductor cross-sections for auxiliary contacts finely stranded with core end processing | 2x (0.5 ... 1.5 mm²) |
| ● type of connectable conductor cross-sections for auxiliary contacts finely stranded without core end processing | 2x (0.5 ... 1.5 mm²) |
| General Product ApprovalFor use in hazardous locationsDeclaration of ConformityTest CertificatesMarine / ShippingMiscellaneousType Test Certificates/Test ReportSpecial Test CertificateMarine / ShippingotherMiscellaneousConfirmationRailwaySpecial Test Certificate | General Product Approval |
Technical specifications and performance data
Installation and operation guide