Service time: Monday to Friday 9:00-18:00
3RT2035-1NE30 - 3RT2035-1NE30 SIEMENS power contactor, AC-3 40 A, 18.5 kW / 400 V 1 NO + 1 NC, AC / DC 48-80 V, with varisto..
In Stock Hot Product

3RT2035-1NE30

3RT2035-1NE30 SIEMENS power contactor, AC-3 40 A, 18.5 kW / 400 V 1 NO + 1 NC, AC / DC 48-80 V, with varisto..

$0.00USD
3214 in stock
Key Specifications
:
EAN:4011209939455
UPC:Not available
ETIM:5
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
EAN4011209939455
UPCNot available
ETIM5
IDEA4
depth130 mm
width55 mm
UNSPSC15
eClass6
height114 mm
● at AC7.7g / 5 ms, 4.5g / 10 ms
● at DC7.7g / 5 ms, 4.5g / 10 ms
Group CodeR711
arcing time10 ... 20 ms
— upwards10 mm
● at AC-1
● at AC-3
Metal FactorLDP-----
— forwards10 mm
● at 50 Hz0.8 ... 1.1
● at 60 Hz0.8 ... 1.1
● at AC-3e
● at AC-6a
Date5/14/2022Subject to change without notice© Copyright Siemens 2022
Product Group5338
Product classC: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
Quantity Unit1 Piece
closing delay
opening delay
— downwards10 mm
Commodity Code85364900
Product familySIRIUS 3RT contactors, 3-pole, up to 250 kW
last modified:2/15/2022
Net Weight (kg)1,115 Kg
operating power
— at the side0 mm
● rated value48 ... 80 V
fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
product function
required spacing
Country of originGermany
Marine / Shippingother
Test CertificatesMarine / Shipping
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
operating voltage
product extension
size of contactorS2
● initial value0.8
LKZ_FDB/ CatalogIDCC-IC10
Packaging Quantity1
insulation voltage
product brand nameSIRIUS
● during storage-55 ... +80 °C
● for live parts
● of magnet coilScrew-type terminals
Packaging Dimension62,00 x 123,00 x 149,00
Product Descriptionpower contactor, AC-3 40 A, 18.5 kW / 400 V 1 NO + 1 NC, AC / DC 48-80 V, with varistor, 3-pole, Size S2, screw terminal
ambient temperature
inrush current peak1 A
operating frequency
operational current
product designationPower contactor
suitability for use
● at AC-1 maximum1 200 1/h
● at AC-2 maximum750 1/h
● at AC-3 maximum1 000 1/h
● at AC-4 maximum300 1/h
● at AC-3e maximum1 000 1/h
● auxiliary switchYes
● during operation-25 ... +60 °C
● full-scale value1.1
— solid or stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
● for main contacts
● solid or stranded0.5 ... 2.5 mm²
● for grounded parts
Product Lifecycle (PLM)PM300:Active Product
design of the fuse link
— at 24 V rated value55 A
● at 24 V rated value10 A
● at 48 V rated value6 A
● at 60 V rated value6 A
General Product ApprovalEMC
Special Test Certificate
product type designation3RT2
surge voltage resistance
— at 110 V rated value4.5 A
— at 220 V rated value1 A
— at 230 V rated value11 kW
— at 400 V rated value41 A
— at 440 V rated value0.4 A
— at 500 V rated value41 A
— at 600 V rated value0.25 A
— at 690 V rated value24 A
● at 110 V rated value3 A
● at 125 V rated value2 A
● at 220 V rated value1 A
● at 230 V rated value10 A
● at 400 V rated value22 A
● at 480 V rated value40 A
● at 50 Hz rated value48 ... 80 V
● at 500 V rated value2 A
● at 60 Hz rated value48 ... 80 V
● at 600 V rated value0.15 A
● at 690 V rated value18.5 A
● for 3-phase AC motor
● of contactor typical10 000 000
locked-rotor current peak1 A
relative humidity minimum10 %
● side-by-side mountingYes
Export Control RegulationsAL : N / ECCN : N
Modular version (EF001126)true
holding current mean value15 mA
● for auxiliary contacts
Standard lead time ex-works50 Day/Days
Surcharge for Raw MaterialsNone
no-load switching frequency
Package size unit of measureMM
control supply voltage at AC
control supply voltage at DC
operational current at AC-15
operational current at DC-12
operational current at DC-13
— at 110/120 V rated value3 hp
— at 200/208 V rated value10 hp
— at 220/230 V rated value15 hp
— at 460/480 V rated value30 hp
— at 575/600 V rated value40 hp
● for main current circuitscrew-type terminals
Substance Prohibitance (Date)10/01/2014
type of electrical connection
● at 1 current path at DC-1
● for single-phase AC motor
design of the surge suppressorwith varistor
● with side-by-side mounting
duration of inrush current peak30 µs
locked-rotor current mean value0.5 A
● at AC-3 rated value maximum690 V
● of main circuit rated value6 kV
duration of locked-rotor current230 ms
proportion of dangerous failures
shock resistance with sine pulse
● at AC in hot operating state6.6 W
● at AC-2 at 400 V rated value18.5 kW
● at AC-3e rated value maximum690 V
● at AC-4 at 400 V rated value35 A
● safety-related switching OFFYes
operating apparent power at AC-6a
closing power of magnet coil at DC23 W
holding power of magnet coil at DC1 W
yielded mechanical performance [hp]
● at AWG cables for main contacts2x (18 ... 2), 1x (18 ... 1)
operational current at AC-12 maximum10 A
● at AC-5a up to 690 V rated value52.8 A
● at AC-5b up to 400 V rated value33.2 A
● of auxiliary circuit rated value6 kV
Article Number (Market Facing Number)3RT2035-1NE30
Rated operation power NEMA (EF011960)22.0649625
Voltage type for actuating (EF008242)AC/DC
● at 1 current path at DC-3 at DC-5
● for auxiliary and control circuitscrew-type terminals
● function module for communicationNo
WEEE (2012/19/EU) Take-Back ObligationYes
— with type of assignment 2 requiredgG: 80A (690V,100kA), aM: 50A (690V,100kA), BS88: 63A (415V,80kA)
● without load current share typical2 W
number of NO contacts for main contacts3
reference code according to IEC 81346-2Q
shock resistance at rectangular impulse
● at contactor for auxiliary contactsScrew-type terminals
number of poles for main current circuit3
— with type of coordination 1 requiredgG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
● at AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
● at AC in hot operating state per pole2.2 W
mechanical service life (switching cycles)
● with 2 current paths in series at DC-1
● with 3 current paths in series at DC-1
apparent holding power of magnet coil at AC
apparent pick-up power of magnet coil at AC
full-load current (FLA) for 3-phase AC motor
type of connectable conductor cross-sections
— finely stranded with core end processing2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● finely stranded with core end processing1 ... 35 mm²
power loss [W] for rated value of the current
type of voltage of the control supply voltageAC/DC
● mirror contact according to IEC 60947-4-1Yes
● with low demand rate according to SN 3192040 %
Rated operation power at AC-3, 400 V (EF001364)18.5
Rated operation power at AC-4, 400 V (EF008496)-
● with high demand rate according to SN 3192073 %
Rated control supply voltage Us at DC (EF003980)['48', '80']
control version of the switch operating mechanismStandard A1 - A2
● with 2 current paths in series at DC-3 at DC-5
● with 3 current paths in series at DC-3 at DC-5
Rated operation current Ie at AC-1, 400 V (EF001393)60
Rated operation current Ie at AC-3, 400 V (EF001392)40
Rated operation current Ie at AC-4, 400 V (EF008495)35
Region Specific PriceGroup / Headquarter Price Group41B / 41B
contact rating of auxiliary contacts according to ULA600 / P600
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
● for short-circuit protection of the main circuit
● limited to 1 s switching at zero current maximum843 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum596 A; Use minimum cross-section acc. to AC-1 rated value
B10 value with high demand rate according to SN 319201 000 000
Rated control supply voltage Us at AC 50HZ (EF003978)['48.0', '80.0']
Rated control supply voltage Us at AC 60HZ (EF003979)['48.0', '80.0']
connectable conductor cross-section for main contacts
● limited to 10 s switching at zero current maximum400 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum241 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum196 A; Use minimum cross-section acc. to AC-1 rated value
AWG number as coded connectable conductor cross section
installation altitude at height above sea level maximum2 000 m
protection class IP on the front according to IEC 60529IP20
— up to 230 V for current peak value n=20 rated value36.5 A
— up to 230 V for current peak value n=30 rated value24.2 A
— up to 400 V for current peak value n=20 rated value36.5 A
— up to 400 V for current peak value n=30 rated value24.2 A
— up to 500 V for current peak value n=20 rated value36.5 A
— up to 500 V for current peak value n=30 rated value24.2 A
— up to 690 V for current peak value n=20 rated value24 A
— up to 690 V for current peak value n=30 rated value24 A
● up to 230 V for current peak value n=20 rated value14.5 kVA
● up to 230 V for current peak value n=30 rated value9.6 kVA
● up to 400 V for current peak value n=20 rated value25.2 kVA
● up to 400 V for current peak value n=30 rated value16.8 kVA
● up to 500 V for current peak value n=20 rated value31.6 kVA
● up to 500 V for current peak value n=30 rated value21 kVA
● up to 690 V for current peak value n=20 rated value28.6 kVA
● up to 690 V for current peak value n=30 rated value28.6 kVA
Type of electrical connection of main circuit (EF006819)Screw connection
— up to 690 V at ambient temperature 40 °C rated value60 A
— up to 690 V at ambient temperature 60 °C rated value55 A
connectable conductor cross-section for auxiliary contacts
● of main circuit with degree of pollution 3 rated value690 V
● positively driven operation according to IEC 60947-5-1No
Number of main contacts as normally open contact (EF001374)3
operating power for approx. 200000 operating cycles at AC-4
Number of normally closed contacts as main contact (EF001375)-
failure rate [FIT] with low demand rate according to SN 31920100 FIT
● at AC-1 at 400 V at ambient temperature 40 °C rated value60 A
● of the contactor with added auxiliary switch block typical10 000 000
operational current for approx. 200000 operating cycles at AC-4
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
● of auxiliary circuit with degree of pollution 3 rated value690 V
Number of auxiliary contacts as normally open contact (EF001376)1
minimum cross-section in main circuit at maximum AC-1 rated value16 mm²
short-time withstand current in cold operating state up to 40 °C
● for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Number of auxiliary contacts as normally closed contact (EF001377)1
number of NC contacts for auxiliary contacts instantaneous contact1
number of NO contacts for auxiliary contacts instantaneous contact1
Compliance with the substance restrictions according to RoHS directiveSince: 01.10.2014
REACH Art. 33 Duty to inform according to the current list of candidatesLead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
operating range factor control supply voltage rated value of magnet coil at AC
operating range factor control supply voltage rated value of magnet coil at DC
● of the contactor with added electronically optimized auxiliary switch block typical5 000 000
maximum permissible voltage for safe isolation between coil and main contacts according to EN 60947-1400 V
General Product ApprovalConfirmationMiscellaneousKCGeneral Product ApprovalEMCFunctional Safety/Safety of MachineryDeclaration of ConformityTest CertificatesType Examination CertificateUK Declaration of ConformityType Test Certificates/Test ReportTest CertificatesMarine / ShippingSpecial Test CertificateMarine / ShippingotherRailwayDangerous GoodConfirmationConfirmationVibration and ShockTransport InformationGeneral Product Approval

Product Description

CONTACTOR 3 POLES, SIZE S2, 40A AC-3, AC/DC 48-80V, 18.5KW / 400V, 1NA+1NC, SCREW TERMINALS. Manufactured to order. Non-Cancelable Non-Returnable.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top