| Parameter | Value |
|---|---|
| Value | |
| EAN | 4011209394445 |
| UPC | 754554502069 |
| Depth | 115 mm |
| Notes | Sucessor:Successor SIRIUS Innovation 3RT2This product is a Spare Part, please visit the Spares & Service section for more informationIf you need assistance please contact our local Siemens office |
| Width | 73 mm |
| Height | 112 mm |
| — solid | 2x (0.75 ... 16 mm²) |
| ● at AC | 4 ... 35 ms |
| Group Code | R711 |
| Arcing time | 10 ... 15 ms |
| Price Group | 41B |
| ● at AC-1 | |
| ● maximum | 2 000 m |
| Metal Factor | LFO----- |
| — stranded | 2x (0.75 ... 25 mm²) |
| ● at 50 Hz | 0.8 ... 1.1 |
| ● at 60 Hz | 0.8 ... 1.1 |
| Closing delay | |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| Opening delay | |
| Product Group | 3705 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85364900 |
| Product family | Not available |
| last modified: | 08/13/2020 |
| Net Weight (kg) | 0,983 Kg |
| Operating power | |
| — at the side | 6 mm |
| Required spacing | |
| Country of origin | Germany |
| Marine / Shipping | other |
| Operating current | |
| Size of contactor | S2 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| PLM Effective Date | Product is cancelled since: 01.10.2019 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| Ambient temperature | |
| Operating frequency | |
| Packaging Dimension | 82,00 x 118,50 x 137,00 |
| Product Description | Power contactor, AC-3 40 A, 18.5 kW / 400 V 240 V AC, 60 Hz 4-pole, 2 NO + 2 NC Size S2, Screw terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2 |
| Product designation | power contactor |
| ● at AC-1 maximum | 1 000 1/h |
| ● at AC-2 at AC-3 | |
| ● during operation | -25 ... +60 °C |
| ● for main contacts | |
| ● mounting position | with vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back |
| ● for grounded parts | |
| Design of the fuse link | |
| Product Lifecycle (PLM) | PM410:Product cancellation |
| — at 24 V rated value | 50 A |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 6 A |
| General Product Approval | EMC |
| Surge voltage resistance | |
| — at 110 V rated value | 4.5 A |
| — at 220 V rated value | 1 A |
| — at 440 V rated value | 0.4 A |
| ● at 110 V rated value | 3 A |
| ● at 220 V rated value | 1 A |
| ● at 230 V rated value | 6 A |
| ● at 400 V rated value | 3 A |
| ● at 50 Hz rated value | 220 V |
| ● at 60 Hz rated value | 240 V |
| ● of contactor typical | 10 000 000 |
| Declaration of Conformity | Test Certificates |
| ● Side-by-side mounting | Yes |
| ● instantaneous contact | 0 |
| Export Control Regulations | ECCN : N / AL : N |
| Modular version (EF001126) | true |
| Operating current at AC-15 | |
| Operating current at DC-12 | |
| Operating current at DC-13 | |
| ● for auxiliary contacts | |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| Control supply voltage at AC | |
| Package size unit of measure | MM |
| — single or multi-stranded | 2x (0,75 ... 16 mm²) |
| ● at AC-2 at AC-3 at 400 V | |
| ● at 1 current path at DC-1 | |
| Product Dimensions (W x L x H) | Not available |
| — per NC contact rated value | 40 A |
| — per NO contact rated value | 40 A |
| ● at maximum AC-1 rated value | 16 mm² |
| ● of main circuit rated value | 6 kV |
| Operating current at AC-12 maximum | 10 A |
| Protection against electrical shock | finger-safe |
| ● of auxiliary circuit rated value | 6 kV |
| ● protection class IP on the front | IP20 |
| Article Number (Market Facing Number) | 3RT1535-1AP60 |
| Minimum cross-section in main circuit | |
| Rated operation power NEMA (EF011960) | - |
| Reference code acc. to DIN EN 81346-2 | Q |
| Voltage type for actuating (EF008242) | AC |
| ● at 1 current path at DC-3 at DC-5 | |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| — at 24 V per NC contact rated value | 35 A |
| — at 24 V per NO contact rated value | 35 A |
| — with type of assignment 2 required | fuse gL/gG: 80 A |
| ● at AC at 230 V maximum permissible | 0.018 A |
| Number of NC contacts for main contacts | 2 |
| Number of NO contacts for main contacts | 2 |
| — at 110 V per NC contact rated value | 1.25 A |
| — at 110 V per NO contact rated value | 2.5 A |
| — at 220 V per NC contact rated value | 0.5 A |
| — at 220 V per NO contact rated value | 1 A |
| — at 230 V per NC contact rated value | 9.5 kW |
| — at 230 V per NO contact rated value | 9.5 kW |
| — at 400 V per NC contact rated value | 18.5 kW |
| — at 400 V per NO contact rated value | 18.5 kW |
| — at 440 V per NC contact rated value | 0.05 A |
| — at 440 V per NO contact rated value | 0.1 A |
| ● Protection class IP of the terminal | IP00 |
| ● at AWG conductors for main contacts | 2x (18 ... 2) |
| Number of poles for main current circuit | 4 |
| — with type of coordination 1 required | fuse gL/gG: 160 A |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Mechanical service life (switching cycles) | |
| ● with 2 current paths in series at DC-1 | |
| Apparent holding power of magnet coil at AC | 12.6 V·A |
| Apparent pick-up power of magnet coil at AC | 166 V·A |
| Number of NC contacts for auxiliary contacts | |
| Number of NO contacts for auxiliary contacts | |
| Type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (0.75 ... 16 mm²) |
| ● at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
| Type of voltage of the control supply voltage | AC |
| Installation altitude at height above sea level | |
| Rated operation power at AC-3, 400 V (EF001364) | 18.5 |
| Rated operation power at AC-4, 400 V (EF008496) | - |
| — finely stranded without core end processing | 2x (0.75 ... 16 mm²) |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| Control version of the switch operating mechanism | conventional |
| ● with 2 current paths in series at DC-3 at DC-5 | |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 60 |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 40 |
| Rated operation current Ie at AC-4, 400 V (EF008495) | - |
| ● for short-circuit protection of the main circuit | |
| Inductive power factor with closing power of the coil | 0.71 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Inductive power factor with the holding power of the coil | 0.37 |
| — up to 690 V at ambient temperature 40 °C rated value | 60 A |
| — up to 690 V at ambient temperature 60 °C rated value | 55 A |
| ● Type of electrical connection for main current circuit | screw-type terminals |
| Number of main contacts as normally open contact (EF001374) | 2 |
| Number of normally closed contacts as main contact (EF001375) | 2 |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| Residual current of the electronics for control with signal <0> | |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| ● for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● Type of electrical connection for auxiliary and control current circuit | screw-type terminals |
| ● Insulation voltage of main circuit with degree of pollution 3 rated value | 690 V |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| ● Insulation voltage of auxiliary circuit with degree of pollution 3 rated value | 690 V |
| ● of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
| Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor | 2.6 W |
| General Product ApprovalEMCFunctional Safety/Safety of MachineryType Examination CertificateDeclaration of ConformityTest CertificatesMarine / ShippingMiscellaneousSpecial Test CertificateMarine / ShippingotherRailwayConfirmationMiscellaneousSpecial Test Certificate | General Product Approval |
Technical specifications and performance data