| Parameter | Value |
|---|---|
| Value | |
| EAN | 4011209396241 |
| UPC | 887621848255 |
| Depth | 164 mm |
| Notes | Sucessor:Successor Innovation 3R.2This product is a Spare Part, please visit the Spares & Service section for more informationIf you need assistance please contact our local Siemens office |
| Width | 55 mm |
| Height | 112 mm |
| — solid | 2x (0.75 ... 16 mm²) |
| ● at AC | 10g / 5 ms, 5g / 10 ms |
| Group Code | R711 |
| Arcing time | 10 ... 15 ms |
| Price Group | 41B |
| ● at AC-1 | |
| ● at AC-3 | |
| ● maximum | 2 000 m |
| Metal Factor | LFO----- |
| — stranded | 2x (0.75 ... 25 mm²) |
| ● at 50 Hz | 0.8 ... 1.1 |
| Closing delay | |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| Opening delay | |
| Product Group | 3705 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85364900 |
| Product family | Not available |
| last modified: | 08/13/2020 |
| Net Weight (kg) | 0,921 Kg |
| Operating power | |
| — at the side | 6 mm |
| Required spacing | |
| Country of origin | Germany |
| Marine / Shipping | other |
| Operating current | |
| Size of contactor | S2 |
| ● 1 rated value | 50 Hz |
| LKZ_FDB/ CatalogID | CC-IC10 |
| PLM Effective Date | Product is cancelled since: 01.10.2019 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| Ambient temperature | |
| Degree of pollution | 3 |
| Operating frequency | |
| Packaging Dimension | 62,50 x 118,00 x 190,00 |
| Product Description | Power contactor, AC-3 40 A, 18.5 kW / 400 V 2 NO + 2 NC, 110 V AC, 50 Hz, 3-pole, Size S2, Main circuit: Screw terminal Auxiliary circuit: Spring-type terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2 Preferred successor type is >>3RT2028-2AF04<< |
| Product designation | power contactor |
| ● at AC-1 maximum | 1 200 1/h |
| ● at AC-2 maximum | 600 1/h |
| ● at AC-3 maximum | 1 000 1/h |
| ● at AC-4 maximum | 300 1/h |
| ● at AC-1 at 400 V | |
| ● during operation | -25 ... +60 °C |
| ● for main contacts | |
| ● for grounded parts | |
| Design of the fuse link | |
| Product Lifecycle (PLM) | PM410:Product cancellation |
| — at 24 V rated value | 55 A |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 6 A |
| General Product Approval | EMC |
| Special Test Certificate | |
| — at 110 V rated value | 4.5 A |
| — at 230 V rated value | 11 kW |
| — at 400 V rated value | 40 A |
| — at 500 V rated value | 22 kW |
| — at 690 V rated value | 24 A |
| ● at 110 V rated value | 3 A |
| ● at 220 V rated value | 1 A |
| ● at 230 V rated value | 6 A |
| ● at 400 V rated value | 18.5 A |
| ● at 50 Hz rated value | 110 V |
| ● at 690 V rated value | 12.6 A |
| ● of contactor typical | 10 000 000 |
| Declaration of Conformity | Test Certificates |
| ● Side-by-side mounting | Yes |
| ● instantaneous contact | 2 |
| Export Control Regulations | ECCN : N / AL : N |
| Modular version (EF001126) | true |
| Operating current at AC-15 | |
| Operating current at DC-12 | |
| Operating current at DC-13 | |
| ● for auxiliary contacts | |
| No-load switching frequency | |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| Control supply voltage at AC | |
| Package size unit of measure | MM |
| — single or multi-stranded | 2x (0,75 ... 16 mm²) |
| ● at 1 current path at DC-1 | |
| Product Dimensions (W x L x H) | Not available |
| Shock resistance with sine pulse | |
| control supply voltage frequency | |
| ● at AC-2 at 400 V rated value | 18.5 kW |
| ● at AC-4 at 400 V rated value | 35 A |
| ● at 40 °C minimum permissible | 16 mm² |
| ● at 60 °C minimum permissible | 16 mm² |
| Operating current at AC-12 maximum | 10 A |
| — at 230 V at 60 °C rated value | 22 kW |
| — at 690 V at 60 °C rated value | 66 kW |
| ● Insulation voltage rated value | 690 V |
| Surge voltage resistance rated value | 6 kV |
| ● protection class IP on the front | IP20 |
| Article Number (Market Facing Number) | 3RT1035-3AF04 |
| Rated operation power NEMA (EF011960) | - |
| Reference code acc. to DIN EN 81346-2 | Q |
| Voltage type for actuating (EF008242) | AC |
| ● at 1 current path at DC-3 at DC-5 | |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| — with type of assignment 2 required | fuse gL/gG: 63 A |
| Number of NC contacts for main contacts | 0 |
| Number of NO contacts for main contacts | 3 |
| Shock resistance at rectangular impulse | |
| ● Protection class IP of the terminal | IP00 |
| ● at AWG conductors for main contacts | 2x (18 ... 2) |
| Number of poles for main current circuit | 3 |
| — with type of coordination 1 required | fuse gL/gG: 125 A |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Mechanical service life (switching cycles) | |
| Thermal short-time current limited to 10 s | 400 A |
| ● with 2 current paths in series at DC-1 | |
| ● with 3 current paths in series at DC-1 | |
| Apparent holding power of magnet coil at AC | 12.5 V·A |
| Apparent pick-up power of magnet coil at AC | 145 V·A |
| Number of NC contacts for auxiliary contacts | |
| Number of NO contacts for auxiliary contacts | |
| Type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (0.75 ... 16 mm²) |
| ● at AWG conductors for auxiliary contacts | 2x (24 ... 14) |
| Type of voltage of the control supply voltage | AC |
| — at ambient temperature 40 °C rated value | 60 A |
| maximum permissible voltage for safe isolation | |
| Installation altitude at height above sea level | |
| Rated operation power at AC-3, 400 V (EF001364) | 18.5 |
| Rated operation power at AC-4, 400 V (EF008496) | 18.5 |
| — finely stranded without core end processing | 2x (0.75 ... 16 mm²) |
| Rated control supply voltage Us at DC (EF003980) | - |
| ● with 2 current paths in series at DC-3 at DC-5 | |
| ● with 3 current paths in series at DC-3 at DC-5 | |
| Contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 60 |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 40 |
| Rated operation current Ie at AC-4, 400 V (EF008495) | 35 |
| ● for short-circuit protection of the main circuit | |
| Inductive power factor with closing power of the coil | 0.79 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['110', '110'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| ● between coil and main contacts acc. to EN 60947-1 | 400 V |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Inductive power factor with the holding power of the coil | 0.36 |
| — up to 690 V at ambient temperature 40 °C rated value | 60 A |
| — up to 690 V at ambient temperature 60 °C rated value | 55 A |
| ● Type of electrical connection for main current circuit | screw-type terminals |
| Connectable conductor cross-section in main circuit at AC-1 | |
| Number of main contacts as normally open contact (EF001374) | 3 |
| Operating power for approx. 200000 operating cycles at AC-4 | |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Operating current for approx. 200000 operating cycles at AC-4 | |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| Number of auxiliary contacts as normally open contact (EF001376) | 2 |
| ● for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
| Number of auxiliary contacts as normally closed contact (EF001377) | 2 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● Type of electrical connection for auxiliary and control current circuit | spring-loaded terminals |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| ● of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
| General Product ApprovalEMCFunctional Safety/Safety of MachineryType Examination CertificateDeclaration of ConformityTest CertificatesMarine / ShippingMiscellaneousSpecial Test CertificateType Test Certificates/Test ReportMiscellaneousMarine / ShippingotherConfirmationMiscellaneousRailwaySpecial Test Certificate | General Product Approval |
Technical specifications and performance data
Installation and operation guide