| Parameter | Value |
|---|---|
| EAN | 4047621050324 |
| UPC | 804766715136 |
| ETIM | 5 |
| depth | 90 mm |
| width | 22.5 mm |
| eClass | 6 |
| height | 100 mm |
| ● at DC | 24 ... 240 V |
| ● solid | 0.5 ... 4 mm² |
| Group Code | R711 |
| ● at 24 V | 1 A |
| Date5/9/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | LA------ |
| ● at 125 V | 0.2 A |
| ● at 250 V | 0.1 A |
| ● at 50 Hz | 24 ... 240 V |
| ● at 60 Hz | 24 ... 240 V |
| ● stranded | 12 ... 20 |
| ON-delay time | |
| Product Group | 4949 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85364900 |
| OFF-delay time | 100 ms |
| Product family | SIRIUS 3RQ2 coupling relays with industrial enclosure |
| last modified: | 1/26/2022 |
| Net Weight (kg) | 0,158 Kg |
| type of voltage | AC/DC |
| Depth (EF000049) | 90.0 |
| Width (EF000008) | 22.5 |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| shock resistance | |
| Country of origin | Germany |
| Height (EF000040) | 100.0 |
| Marine / Shipping | other |
| mounting position | any |
| ● at AC maximum | 10 ms |
| ● at DC maximum | 10 ms |
| ● initial value | 0.7 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| switching behavior | monostable |
| ● during storage | -40 ... +80 °C |
| Packaging Dimension | 105,00 x 135,00 x 35,00 |
| Product Description | Coupling relay in industrial enclosure 1 changeover contact Wide voltage range 24 V to 240 V AC/DC Spring-type terminals |
| ambient temperature | |
| degree of pollution | 3 |
| product designation | Coupling relay in industrial enclosure |
| protection class IP | IP20 |
| vibration resistance | |
| ● during operation | -40 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| ● full-scale value | 1.1 |
| consumed active power | 4 W |
| conducted interference | |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at 24 V at 50/60 Hz | 3 A |
| ● at AWG cables solid | 20 ... 12 |
| General Product Approval | EMC |
| control supply voltage 1 | |
| product type designation | 3RQ2 |
| ● at 110 V at 50/60 Hz | 3 A |
| ● at 250 V at 50/60 Hz | 3 A |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | AL : N / ECCN : N |
| Nominal current (EF000001) | - |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| UK Declaration of Conformity | |
| Substance Prohibitance (Date) | 05/31/2018 |
| electromagnetic compatibility | IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4 |
| type of electrical connection | spring-loaded terminal (push-in) |
| Drive, polarization (EF003355) | Polarized |
| With LED indication (EF005950) | - |
| control supply voltage 1 at AC | |
| material of switching contacts | AgSnO2 |
| ● according to IEC 60068-2-6 | 10 ... 55 Hz: 0.35 mm |
| Complete with socket (EF003359) | false |
| ● according to IEC 60068-2-27 | 11g / 15 ms |
| product component plug-in socket | No |
| Type of switch contact (EF003358) | - |
| With detachable clamps (EF003340) | false |
| relative humidity during operation | 10 ... 95 % |
| connectable conductor cross-section | |
| Degree of protection (IP) (EF005474) | IP20 |
| Drive, switching attitude (EF003356) | Mono stable |
| surge voltage resistance rated value | 4 kV |
| Article Number (Market Facing Number) | 3RQ2000-2AW00 |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| Voltage type for actuating (EF008242) | AC/DC |
| ampacity of the output relay at AC-15 | |
| ampacity of the output relay at DC-13 | |
| Type of electric connection (EF003961) | Spring clamp connection |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| With forced-guided contacts (EF003357) | false |
| design of the relay operating mechanism | poled |
| reference code according to IEC 81346-2 | K |
| contact reliability of auxiliary contacts | one incorrect switching operation of 100 million switching operations (17 V, 5 mA) |
| ● between auxiliary and auxiliary circuit | 300 V |
| ● due to burst according to IEC 61000-4-4 | 2 kV |
| number of CO contacts for auxiliary contacts | 1 |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 0.5 ... 2.5 mm² |
| maximum permissible voltage for safe isolation | |
| ● finely stranded without core end processing | 0.5 mm² |
| Rated control supply voltage Us at DC (EF003980) | ['24', '240'] |
| EMC emitted interference according to IEC 60947-1 | ambience A (industrial sector) |
| electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharging, 8 kV air discharging |
| mechanical service life (switching cycles) typical | 10 000 000 |
| ● for railway applications according to EN 61373 | Category 1, Class B |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Number of contacts as change-over contact (EF008257) | 1 |
| Region Specific PriceGroup / Headquarter Price Group | 41H / 41H |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['24', '240'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['24', '240'] |
| Number of contacts as normally open contact (EF008256) | 0 |
| AWG number as coded connectable conductor cross section | |
| installation altitude at height above sea level maximum | 2 000 m |
| Number of contacts as normally closed contact (EF008255) | 0 |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV (line to ground) |
| thermal current of the switching element with contacts maximum | 5 A |
| operating range factor control supply voltage rated value at DC | |
| stripped length of the cable for auxiliary and control contacts | 10 mm |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV (line to line) |
| electrical endurance (switching cycles) at AC-15 at 230 V typical | 100 000 |
| ● between control and auxiliary circuit according to IEC 60947-1 | 300 V |
| Compliance with the substance restrictions according to RoHS directive | Since: 31.05.2018 |
| product component removable terminal for auxiliary and control circuit | Yes |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| operating range factor control supply voltage rated value at AC at 50 Hz | |
| operating range factor control supply voltage rated value at AC at 60 Hz | |
| design of the fuse link for short-circuit protection of the auxiliary switch required | fuse gL/gG: 6 A |
| insulation voltage for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value | 300 V |
| General Product ApprovalEMCConfirmationDeclaration of ConformityTest CertificatesMarine / ShippingUK Declaration of ConformityType Test Certificates/Test ReportMarine / ShippingotherRailwayConfirmationConfirmation | General Product Approval |