| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4047621012292 |
| UPC | 804766246487 |
| ETIM | 5 |
| MTBF | 46 y |
| depth | 150 mm |
| width | 30 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 142 mm |
| ● note | 4 via 3DI/LC module |
| Group Code | R711 |
| safe state | Load circuit open |
| trip class | CLASS OFF / 5 / 10 adjustable |
| ● upwards | 50 mm |
| Confirmation | |
| Date5/3/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | None |
| ON-delay time | 20 ms |
| Product Group | 3724 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● downwards | 50 mm |
| Commodity Code | 85371098 |
| OFF-delay time | 35 ... 50 ms |
| Product family | ET 200SP motor starters |
| last modified: | 10/22/2021 |
| Net Weight (kg) | 0,534 Kg |
| Depth (EF000049) | 150.0 |
| Width (EF000008) | 30.0 |
| fastening method | pluggable in BaseUnit |
| minimum load [%] | 50 %; from smallest adjustable rated current |
| product category | Motor starter |
| product function | Direct-on-line starter |
| shock resistance | 6g / 11 ms |
| ● direct start | Yes |
| Country of origin | Germany |
| Height (EF000040) | 142.0 |
| mounting position | Vertical, horizontal (observe derating) |
| ● of the inputs | 4 byte |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIMATIC |
| type of assignment | 1 |
| ● during storage | -40 ... +70 °C |
| ● of the outputs | 2 byte |
| Packaging Dimension | 70,00 x 164,00 x 185,00 |
| Product Description | Direct-on-line starter High Feature; Electronic switching; Electronic overload protection up to 4 kW / 400 V; Adjustment range 2.8 .. 9 A; PROFIenergy; Option: 3DI/LC module |
| ambient temperature | |
| degree of pollution | 2 |
| operational current | |
| product designation | Direct-on-line starter |
| With fuse (EF006693) | - |
| overvoltage category | III |
| utilization category | |
| vibration resistance | 15 mm to 6 Hz; 2g to 500 Hz |
| ● during operation | 140 mA |
| ● during transport | -40 ... +70 °C |
| ● reverse starting | No |
| protocol is supported | |
| ● PROFINET protocol | Yes |
| ● on-site operation | Yes |
| conducted interference | |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● maximum permissible | 28.8 V |
| ● minimum permissible | 20.4 V |
| General Product Approval | EMC |
| Release class (EF006668) | Other |
| number of digital inputs | 4 |
| product type designation | ET 200SP |
| — at 230 V rated value | 1 hp |
| ● PROFIBUS DP protocol | Yes |
| ● at 400 V rated value | 55 kA |
| ● at 500 V rated value | 55 kA |
| ● for 3-phase AC motor | |
| Declaration of Conformity | Test Certificates |
| ● at 40 °C rated value | 9 A |
| ● at 50 °C rated value | 9 A |
| ● at 55 °C rated value | 9 A |
| ● at 60 °C rated value | 9 A |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| ● for main energy infeed | Plug contact to Base Unit |
| ● remote firmware update | Yes |
| Standard lead time ex-works | 60 Day/Days |
| Surcharge for Raw Materials | None |
| With transformer (EF000278) | false |
| inrush current peak at 24 V | 25 A; Observe the manual for group configuration |
| operating frequency maximum | 1 1/s |
| Package size unit of measure | MM |
| type of the motor protection | solid-state |
| — at 110/120 V rated value | 0.33 hp |
| — at 200/208 V rated value | 2 hp |
| — at 220/230 V rated value | 2 hp |
| — at 460/480 V rated value | 5 hp |
| ● at switching on of motor | 230 mA |
| Substance Prohibitance (Date) | 04/15/2016 |
| operating voltage rated value | 48 ... 500 V |
| type of electrical connection | |
| ● for single-phase AC motor | |
| ampacity when starting maximum | 90 A |
| insulation voltage rated value | 500 V |
| ● according to IEC 60947-4-2 | AC-53a: 9 A: (8-0,7: 70-32) |
| ● according to IEC 60947-4-3 | AC-51: 9 A: (1,2-10: 50-360); AC-55a: 4 A: (3-240: 40-6) |
| design of the switching contact | Hybrid |
| ● 1 for digital input signals | Pluggable module - accessory |
| ● intrinsic device protection | Yes |
| Type of motor starter (EF009598) | - |
| supply voltage at DC rated value | 24 V |
| ● for supply voltage line-side | Plug contact to Base Unit |
| ● in standby mode of operation | 85 mA |
| Rail mounting possible (EF003972) | - |
| operating frequency 1 rated value | 50 Hz |
| operating frequency 2 rated value | 60 Hz |
| ● for load-side outgoing feeder | Plug contact to Base Unit |
| ● supports PROFIenergy shutdown | Yes |
| External reset possible (EF003426) | - |
| air pressure according to SN 31205 | 900 ... 1 060 hPa |
| design of short-circuit protection | fuse |
| product function bus communication | Yes |
| relative humidity during operation | 10 ... 95 % |
| supply voltage 1 at DC rated value | |
| yielded mechanical performance [hp] | |
| Degree of protection (IP) (EF005474) | IP20 |
| product component motor brake output | No |
| surge voltage resistance rated value | 6 kV |
| Article Number (Market Facing Number) | 3RK1308-0AD00-0CP0 |
| EMC immunity according to IEC 60947-1 | Class A |
| Number of indicator lights (EF001965) | - |
| Rated operation current Ie (EF001443) | 9 |
| Voltage type for actuating (EF008242) | DC |
| With short-circuit release (EF006691) | true |
| address space memory of address range | |
| type of voltage of the supply voltage | DC |
| Degree of protection (NEMA) (EF011959) | - |
| Number of command positions (EF001372) | - |
| Suitable for emergency stop (EF001433) | - |
| Supporting protocol for ASI (EF003051) | false |
| Supporting protocol for CAN (EF003053) | - |
| Supporting protocol for LON (EF003017) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ● between main and auxiliary circuit | 500 V |
| duration of inrush current peak at 24 V | 0.145 ms |
| reference code according to IEC 81346-2 | Q |
| number of poles for main current circuit | 3 |
| wire length for motor unshielded maximum | 200 m |
| ● supports PROFIenergy measured values | Yes |
| Supporting protocol for Modbus (EF003057) | - |
| Supporting protocol for SERCOS (EF006657) | - |
| Supporting protocol for TCP/IP (EF003050) | - |
| product function short circuit protection | Yes |
| Supporting protocol for SUCONET (EF003060) | - |
| Overload release current setting (EF002336) | ['2.8', '9'] |
| Supporting protocol for INTERBUS (EF003054) | - |
| Supporting protocol for PROFIBUS (EF003052) | - |
| protocol is supported AS-Interface protocol | No |
| required spacing with side-by-side mounting | |
| ● due to burst according to IEC 61000-4-4 | 2 kV |
| Supporting protocol for DeviceNet (EF003059) | - |
| Supporting protocol for PROFIsafe (EF007526) | - |
| equipment variant according to IEC 60947-4-2 | 3 |
| Rated power, 460 V, 60 Hz, 3-phase (EF009600) | - |
| Rated power, 575 V, 60 Hz, 3-phase (EF009601) | - |
| ● in switching state ON with bypass circuit | 3.4 W |
| Supporting protocol for EtherNet/IP (EF007521) | - |
| Supporting protocol for PROFINET IO (EF007525) | - |
| Supporting protocol for SafetyBUS p (EF007527) | - |
| maximum permissible voltage for safe isolation | |
| operational current at AC at 400 V rated value | 9 A |
| ● at 500 V according to UL 60947 rated value | 100 kA |
| ● in switching state OFF with bypass circuit | 2 W |
| Rated operation power at AC-3, 400 V (EF001364) | - |
| Supporting protocol for Data-Highway (EF003058) | - |
| Supporting protocol for PROFINET CBA (EF007524) | - |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| power loss [W] for rated value of supply voltage | |
| ● for power supply reverse polarity protection | Yes |
| EMC emitted interference according to IEC 60947-1 | class A |
| Rated operation current at AC-3, 400 V (EF009602) | - |
| Supporting protocol for INTERBUS-Safety (EF006662) | - |
| consumed current for rated value of supply voltage | |
| electrostatic discharge according to IEC 61000-4-2 | 8 kV air discharge |
| Supporting protocol for DeviceNet Safety (EF007520) | - |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 42D / 42D |
| Supporting protocol for other bus systems (EF003062) | - |
| operating power for 3-phase motors at 400 V at 50 Hz | 1.5 ... 4 kW |
| touch protection on the front according to IEC 60529 | finger-safe |
| Ambient temperature, upper operating limit (EF009603) | - |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| breaking capacity maximum short-circuit current (Icu) | |
| Supporting protocol for Foundation Fieldbus (EF007522) | - |
| Temperature compensated overload protection (EF009604) | - |
| relative negative tolerance of the operating frequency | 5 % |
| relative positive tolerance of the operating frequency | 5 % |
| installation altitude at height above sea level maximum | 4 000 m; For derating see manual |
| protection class IP on the front according to IEC 60529 | IP20 |
| relative symmetrical tolerance of the operating voltage | 10 % |
| Coordination class according to IEC 60947-4-3 (EF012390) | Class 1 |
| Rated operation power at AC-3, 230 V, 3-phase (EF009599) | - |
| Type of electrical connection of main circuit (EF006819) | - |
| conducted HF interference emissions according to CISPR11 | Class A for industrial environment |
| field-bound HF interference emission according to CISPR11 | Class A for industrial environment |
| relative symmetrical tolerance of the operating frequency | 5 % |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| type of electrical connection of the communication interface | Plug contact to Base Unit |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | - |
| environmental category during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices) |
| ● due to high-frequency radiation according to IEC 61000-4-6 | Class A |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| Number of auxiliary contacts as normally open contact (EF001376) | - |
| Rated conditional short-circuit current, type 2, 230 V (EF009606) | - |
| Rated conditional short-circuit current, type 2, 400 V (EF009605) | - |
| full-load current (FLA) for 3-phase AC motor at 480 V rated value | 9 A |
| Number of auxiliary contacts as normally closed contact (EF001377) | - |
| operating voltage at AC at 60 Hz according to CSA and UL rated value | 480 V |
| Compliance with the substance restrictions according to RoHS directive | Since: 15.04.2016 |
| Rated conditional short-circuit current, type 1, 480 Y/277 V (EF009607) | - |
| Rated conditional short-circuit current, type 1, 600 Y/347 V (EF009608) | - |
| breaking capacity maximum short-circuit current (Icu) in the IT network | |
| mechanical service life (switching cycles) of the main contacts typical | 30 000 000 |
| REACH Art. 33 Duty to inform according to the current list of candidates | 4,4'-isopropylidened... CAS-No. 80-05-7 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):4,4'-isopropylidenediphenol (Bisphenol A, BPA)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | - |
| adjustable current response value current of the current-dependent overload release | 2.8 ... 9 A |
| General Product ApprovalEMCConfirmationDeclaration of ConformityTest CertificatesMarine / ShippingType Test Certificates/Test ReportotherConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide