| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4011209974609 |
| UPC | 804766359873 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 120 mm |
| width | 22.5 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 100 mm |
| ID1 code | F; Factory setting, changeable |
| ● note | 46 mA with supply via AS interface / 500 mA with supply via Uaux |
| ● solid | 1x (0.5 ... 2.5 mm²), 2x ( 0.5 ... 1.5 mm²) |
| Group Code | R711 |
| Metal Factor | None |
| Date5/14/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 3720 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85371098 |
| Product family | SlimLine Compact |
| last modified: | 12/18/2020 |
| reference code | |
| Net Weight (kg) | 0,245 Kg |
| display version | |
| Depth (EF000049) | 120.0 |
| Width (EF000008) | 22.5 |
| fastening method | screw and snap-on mounting |
| shock resistance | 15g / 11 ms (modules) or 10g / 11 ms (modules with device connector) |
| Country of origin | Germany |
| Height (EF000040) | 100.0 |
| Marine / Shipping | other |
| Test Certificates | Marine / Shipping |
| other information | An auxiliary external feed (AUX POWER) of between 20 and 30 V DC is necessary for supplying the output circuits. The auxiliary feed must comply with IEC 60990 (PELV), protection class III. |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| ● during storage | -40 ... +85 °C |
| Packaging Dimension | 111,00 x 159,00 x 38,00 |
| Product Description | AS-i SlimLine Compact module SC22.5, IP20, analog, 4AI-C/V Screw terminals 4 x analog input Inputs switchable C/V Overall width 22.5 mm |
| ambient temperature | |
| product designation | Slimline Compact I/O module for use in the control cabinet |
| protection class IP | IP20 |
| ● at 30 V maximum | 200 mA |
| ● during operation | -25 ... +70 °C |
| ● for AS-Interface | LED green/red |
| design of the product | AS-i SC22.5, 4AI PT100 |
| Product Lifecycle (PLM) | PM300:Active Product |
| number of analog inputs | 4 |
| ● at AWG cables solid | 1x (20 ... 14), 2x (18 ... 16) |
| General Product Approval | EMC |
| design of the slave type | standard slave |
| number of analog outputs | 0 |
| number of digital inputs | 0 |
| IO link master (EF007298) | false |
| Input, current (EF003204) | - |
| Input, voltage (EF003205) | - |
| number of digital outputs | 0 |
| AS-Interface slave profile | S-7.3.E |
| Export Control Regulations | AL : N / ECCN : N |
| Input, resistor (EF003206) | - |
| Output, current (EF003212) | - |
| Output, voltage (EF003213) | - |
| ● at AWG cables stranded | Not permitted |
| Standard lead time ex-works | 10 Day/Days |
| Surcharge for Raw Materials | None |
| System accessory (EF004118) | true |
| ● according to EN 61346-2 | K |
| Package size unit of measure | MM |
| Supply voltage DC (EF007534) | ['-', '-'] |
| Radio standard GSM (EF008524) | false |
| type of connection technology | 2- and 4-wire technology |
| Input, thermocouple (EF003208) | - |
| Radio standard GPRS (EF008523) | false |
| Radio standard UMTS (EF008525) | false |
| signal range at the analog input | 4 ... 20 mA; +/- 20 mA; 1 ... 5 V; +/- 10 V |
| Rack-assembly possible (EF007018) | FALSE |
| Rail mounting possible (EF003972) | FALSE |
| Front build in possible (EF007016) | FALSE |
| Supply voltage AC 50 Hz (EF007532) | ['-', '-'] |
| Supply voltage AC 60 Hz (EF007533) | ['-', '-'] |
| Type Test Certificates/Test Report | |
| ● for external auxiliary voltage | 4 A |
| Radio standard Bluetooth (EF007178) | false |
| Degree of protection (IP) (EF005474) | IP20 |
| Number of analogue inputs (EF001994) | 4 |
| Article Number (Market Facing Number) | 3RK1207-0CE00-2AA2 |
| Input signal, configurable (EF003209) | true |
| Number of analogue outputs (EF001995) | 0 |
| Output signal configurable (EF003214) | - |
| Radio standard WLAN 802.11 (EF007179) | false |
| SIL according to IEC 61508 (EF009889) | None |
| Degree of protection (NEMA) (EF011959) | - |
| Number of HW-interfaces USB (EF003025) | - |
| Supporting protocol for ASI (EF003051) | true |
| Supporting protocol for CAN (EF003053) | false |
| Supporting protocol for KNX (EF003055) | false |
| Supporting protocol for LON (EF003017) | false |
| Type of electric connection (EF003961) | Other |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| type of address setting of AS-i slaves | via front addressing socket |
| ● at 24 V with AS-i Power24V maximum | 250 mA |
| Analogue inputs configurable (EF008518) | true |
| number of digital inputs safety-related | 0 |
| type of voltage supply for power supply | AS interface, alternatively U_AUX |
| A/D resolution for analog inputs/outputs | 16 bit |
| Analogue outputs configurable (EF008519) | - |
| Input, resistance thermometer (EF003207) | false |
| Number of HW-interfaces other (EF003027) | 0 |
| Number of interfaces PROFINET (EF006932) | 0 |
| Suitable for safety functions (EF001597) | false |
| Wall mounting/direct mounting (EF007020) | FALSE |
| Category according to EN 954-1 (EF006782) | - |
| Number of HW-interfaces RS-232 (EF003021) | 0 |
| Number of HW-interfaces RS-422 (EF003022) | 0 |
| Number of HW-interfaces RS-485 (EF003023) | 0 |
| Supporting protocol for Modbus (EF003057) | false |
| Supporting protocol for SERCOS (EF006657) | false |
| Supporting protocol for TCP/IP (EF003050) | false |
| Voltage type of supply voltage (EF002991) | - |
| Supporting protocol for SUCONET (EF003060) | false |
| product function smoothing parameterizable | Yes |
| Number of HW-interfaces Wireless (EF006933) | 0 |
| Number of HW-interfaces parallel (EF003026) | 0 |
| Supporting protocol for INTERBUS (EF003054) | false |
| Supporting protocol for PROFIBUS (EF003052) | false |
| product function suitable for AS-i Power24V | Yes |
| protocol is supported AS-Interface protocol | Yes |
| Appendant operation agent (Ex ia) (EF004141) | - |
| Appendant operation agent (Ex ib) (EF004142) | - |
| Explosion safety category for gas (EF003997) | FALSE |
| Resolution of the analogue inputs (EF003575) | 16 |
| Supporting protocol for DeviceNet (EF003059) | false |
| Supporting protocol for PROFIsafe (EF007526) | false |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.25 ... 2.5 mm²), 2x (0.25 ... 1.0 mm²) |
| Explosion safety category for dust (EF003998) | FALSE |
| Number of HW-interfaces serial TTY (EF003024) | 0 |
| Resolution of the analogue outputs (EF003577) | 16 |
| Supporting protocol for EtherNet/IP (EF007521) | false |
| Supporting protocol for PROFINET IO (EF007525) | false |
| Supporting protocol for SafetyBUS p (EF007527) | false |
| Supporting protocol for Data-Highway (EF003058) | false |
| Supporting protocol for PROFINET CBA (EF007524) | false |
| product function input variable parameterizable | Yes |
| ● finely stranded without core end processing | Not permitted |
| ampacity of the interface to the device connector | |
| Supporting protocol for INTERBUS-Safety (EF006662) | false |
| Supporting protocol for DeviceNet Safety (EF007520) | false |
| Region Specific PriceGroup / Headquarter Price Group | 42C / 42C |
| Supporting protocol for other bus systems (EF003062) | false |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 |
| Supporting protocol for Foundation Fieldbus (EF007522) | false |
| type of electrical connection of the inputs and outputs | Screw terminals |
| Performance level according to EN ISO 13849-1 (EF007399) | - |
| consumed current from external auxiliary voltage maximum | 500 mA |
| operating voltage according to AS-Interface specification | 18 ... 31.6 V |
| consumed current from profile conductors of the AS-Interface | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | false |
| Fieldbus connection over separate bus coupler possible (EF004002) | - |
| property of the sensor supply short-circuit and overload resistant | Yes |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| symmetrical temperature error per K relating to input range/output range | 0.01 %/K |
| relative symmetrical linearity error relating to input range/output range | 0.05 % |
| ampacity of the sensor supply for all inputs at ambient temperature 40 °C | 500 mA |
| relative symmetrical operational limit relating to input range/output range | 1 %; full sclae |
| set values of the interference frequency for interference voltage suppression | 50 / 60 Hz |
| ● according to DIN 40719 extended according to IEC 204-2 according to IEC 750 | A |
| design of the sensor at the analog input is supported resistor temperature sensor | No |
| relative symmetrical basic error limit relating to input range/output range at 25 °C | 0.7 % |
| relative symmetrical repeat accuracy relating to input range/output range in settled state 25 °C | 0.1 % |
| General Product ApprovalEMCDeclaration of ConformityConfirmationTest CertificatesMarine / ShippingType Test Certificates/Test ReportMarine / ShippingotherConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide