| Parameter | Value |
|---|---|
| Value | |
| EAN | 4047621070049 |
| UPC | 040892826463 |
| Depth | 117 mm |
| Width | 45 mm |
| Height | 57.5 mm |
| B10 value | |
| ● at AC | 7,3g / 5 ms, 4,7g / 10 ms |
| ● at DC | 10 000 1/h |
| Group Code | R711 |
| Arcing time | 10 ... 15 ms |
| Price Group | 41A |
| — upwards | 10 mm |
| ● maximum | 2 000 m |
| Confirmation | |
| Metal Factor | LBO----- |
| — forwards | 10 mm |
| ● at 50 Hz | 0.8 ... 1.1 |
| ● at 60 Hz | 0.85 ... 1.1 |
| Closing delay | |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail |
| Opening delay | |
| Product Group | 5331 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| — downwards | 10 mm |
| Commodity Code | 85364900 |
| Product family | Not available |
| last modified: | 08/13/2020 |
| Net Weight (kg) | 0,275 Kg |
| — at the side | 0 mm |
| Product function | |
| Required spacing | |
| Country of origin | Germany |
| Product extension | |
| Size of contactor | S00 |
| ● 1 rated value | 50 Hz |
| ● 2 rated value | 60 Hz |
| Failure rate [FIT] | |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| ● for live parts | |
| Ambient temperature | |
| Degree of pollution | 3 |
| Packaging Dimension | 60,00 x 120,00 x 50,00 |
| Product Description | Contactor relay, 6 NO + 2 NC, 208 V AC 50/60 Hz, Size S00, Ring cable lug connection, Captive auxiliary switch, |
| Product designation | Auxiliary contactor |
| Interface (EF000594) | - |
| ● Auxiliary switch | No |
| ● during operation | -25 ... +60 °C |
| ● mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| ● for grounded parts | |
| Design of the fuse link | |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at 24 V rated value | 10 A |
| ● at 60 V rated value | 10 A |
| General Product Approval | EMC |
| Product type designation | 3RH2 |
| ● at 110 V rated value | 3 A |
| ● at 220 V rated value | 1 A |
| ● at 230 V rated value | 6 A |
| ● at 400 V rated value | 3 A |
| ● at 440 V rated value | 0.3 A |
| ● at 50 Hz rated value | 208 V |
| ● at 500 V rated value | 2 A |
| ● at 60 Hz rated value | 208 V |
| ● at 600 V rated value | 0.15 A |
| ● at 690 V rated value | 1 A |
| ● of contactor typical | 10 000 000 |
| ● instantaneous contact | 2 |
| Export Control Regulations | ECCN : EAR99 / AL : N |
| Mounting method (EF000003) | - |
| Operating current at AC-15 | |
| No-load switching frequency | |
| Standard lead time ex-works | 5 Day/Days |
| Surcharge for Raw Materials | None |
| Control supply voltage at AC | |
| Package size unit of measure | MM |
| Type Examination Certificate | |
| Product Dimensions (W x L x H) | Not available |
| With LED indication (EF005950) | - |
| ● with side-by-side mounting | |
| Proportion of dangerous failures | |
| Shock resistance with sine pulse | |
| control supply voltage frequency | |
| Operating current at AC-12 maximum | 10 A |
| Manual operation possible (EF005881) | - |
| Operating frequency at DC-12 maximum | 1 000 1/h |
| Operating frequency at DC-13 maximum | 1 000 1/h |
| Surge voltage resistance rated value | 6 kV |
| ● protection class IP on the front | IP00 |
| Article Number (Market Facing Number) | 3RH2262-4AM20 |
| Functional Safety/Safety of Machinery | Declaration of Conformity |
| Reference code acc. to DIN EN 81346-2 | K |
| Voltage type for actuating (EF008242) | AC |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Design of the miniature circuit breaker | |
| Shock resistance at rectangular impulse | |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| ● with low demand rate acc. to SN 31920 | 40 % |
| Mechanical service life (switching cycles) | |
| ● with high demand rate acc. to SN 31920 | 1 000 000; With 0.3 x Ie |
| Apparent holding power of magnet coil at AC | 5.7 V·A |
| Apparent pick-up power of magnet coil at AC | 37 V·A |
| Connection type auxiliary circuit (EF006820) | Other |
| Number of NC contacts for auxiliary contacts | 2 |
| Number of NO contacts for auxiliary contacts | 6 |
| Operating current at 1 current path at DC-12 | |
| Operating current at 1 current path at DC-13 | |
| Rated operation current Ie, 400 V (EF001378) | 3 |
| Type of voltage of the control supply voltage | AC |
| Installation altitude at height above sea level | |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| Contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Inductive power factor with closing power of the coil | 0.8 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| ● positively driven operation acc. to IEC 60947-5-1 | Yes |
| Identification number and letter for switching elements | 62 E |
| Inductive power factor with the holding power of the coil | 0.25 |
| Operating current with 2 current paths in series at DC-12 | |
| Operating current with 2 current paths in series at DC-13 | |
| Operating current with 3 current paths in series at DC-12 | |
| Operating current with 3 current paths in series at DC-13 | |
| Number of auxiliary contacts as change-over contact (EF003531) | - |
| Number of auxiliary contacts as normally open contact (EF001376) | 6 |
| ● for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
| Number of auxiliary contacts as normally closed contact (EF001377) | 2 |
| T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |
| ● Insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| ● for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 6 A; 0.4 kA |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2009 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| Number of auxiliary contacts as normally open contact, leading (EF007282) | - |
| ● Type of electrical connection for auxiliary and control current circuit | ring cable connection |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| Number of auxiliary contacts as normally closed contact, delayed switching (EF007281) | - |
| General Product ApprovalEMCKCFunctional Safety/Safety of MachineryDeclaration of ConformityTest CertificatesMarine / ShippingType Examination CertificateMiscellaneousType Test Certificates/Test ReportSpecial Test CertificateMarine / ShippingotherConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide