| Parameter | Value |
|---|---|
| VersionClassificationeClass627-37-10-09eClass7.127-37-10-09eClass827-37-10-09eClass927-37-10-09eClass9.127-37-10-09ETIM5EC000010ETIM6EC000010ETIM7EC000010ETIM8EC000010IDEA44755UNSPSC1539-12-15-29 | |
| EAN | 4011209921566 |
| UPC | 804766192562 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 223 mm |
| other | Dangerous Good |
| width | 177.5 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 142 mm |
| — solid | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) |
| ● at AC | 11.8g / 5 ms, 7.4g / 10 ms |
| Group Code | R711 |
| — upwards | 10 mm |
| ● at AC-3 | |
| Confirmation | |
| Date5/2/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | LDO----- |
| — forwards | 10 mm |
| ● at 50 Hz | 0.8 ... 1.1 |
| ● at 60 Hz | 0.85 ... 1.1 |
| Product Group | 5339 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 10 mm |
| Commodity Code | 85364900 |
| Product family | SIRIUS 3RA24 contactor assemblies for star-delta (wye-delta) starting, up to 90 kW |
| last modified: | 12/1/2021 |
| Net Weight (kg) | 3,771 Kg |
| operating power | |
| — at the side | 10 mm |
| fastening method | screw fixing |
| required spacing | |
| Country of origin | Germany |
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| size of contactor | S2 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| ● for live parts | |
| ● of magnet coil | Screw-type terminals |
| Function (EF000030) | Star-delta contactor |
| Packaging Dimension | 249,00 x 326,00 x 237,00 |
| Product Description | Contactor assembly for star-delta (wye-delta) start AC-3, 55 kW/400 V, 230 V AC 50/60 Hz, 3-pole, size S2 screw terminals electrical and mechanical interlock 3 NO + 3 NC integrated |
| ambient temperature | |
| product designation | Contactor assembly for star-delta (wye-delta) start |
| ● during operation | -25 ... +60 °C |
| — solid or stranded | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) |
| ● for main contacts | |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM300:Active Product |
| design of the fuse link | |
| General Product Approval | Declaration of Conformity |
| product type designation | 3RA24 |
| — at 400 V rated value | 55 kW |
| ● at 400 V rated value | 115 A |
| ● at 50 Hz rated value | 230 V |
| ● at 60 Hz rated value | 230 V |
| ● of contactor typical | 10 000 000 |
| ● instantaneous contact | 3 |
| Export Control Regulations | AL : N / ECCN : N |
| ● for auxiliary contacts | |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| operational current at AC-3 | |
| Package size unit of measure | MM |
| ● for main current circuit | screw-type terminals |
| Substance Prohibitance (Date) | 10/01/2014 |
| manufacturer's article number | |
| type of electrical connection | |
| control supply voltage 1 at AC | |
| ● with side-by-side mounting | |
| ● 1 of the supplied contactor | 3RT2037-1AL20 |
| ● 2 of the supplied contactor | 3RT2037-1AL20 |
| ● 3 of the supplied contactor | 3RT2035-1AL20 |
| proportion of dangerous failures | |
| shock resistance with sine pulse | |
| product extension auxiliary switch | No |
| product function bus communication | No |
| operating frequency at AC-3 maximum | 700 1/h |
| ● at AWG cables for main contacts | 2x (18 ... 2), 1x (18 ... 1) |
| ● of the supplied RS assembly kit | 3RA2933-2BB1 |
| Degree of protection (IP) (EF005474) | IP20 |
| Article Number (Market Facing Number) | 3RA2437-8XF32-1AL2 |
| Rated operation power NEMA (EF011960) | - |
| Voltage type for actuating (EF008242) | AC |
| ● for auxiliary and control circuit | screw-type terminals |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| — with type of assignment 2 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 125 A |
| number of NC contacts for main contacts | 0 |
| number of NO contacts for main contacts | 3 |
| reference code according to IEC 81346-2 | Q |
| shock resistance at rectangular impulse | |
| ● at contactor for auxiliary contacts | Screw-type terminals |
| number of poles for main current circuit | 3 |
| — with type of coordination 1 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 250 A |
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
| contact reliability of auxiliary contacts | < 1 error per 100 million operating cycles |
| mechanical service life (switching cycles) | |
| apparent holding power of magnet coil at AC | |
| apparent pick-up power of magnet coil at AC | |
| protocol is supported AS-Interface protocol | No |
| number of NC contacts for auxiliary contacts | |
| number of NO contacts for auxiliary contacts | |
| type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| operating voltage at AC-3 rated value maximum | 690 V |
| type of voltage of the control supply voltage | AC |
| ● with low demand rate according to SN 31920 | 40 % |
| Rated operation power at AC-3, 400 V (EF001364) | 55.0 |
| ● with high demand rate according to SN 31920 | 73 % |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 115 |
| Region Specific PriceGroup / Headquarter Price Group | 41B / 41B |
| contact rating of auxiliary contacts according to UL | A600 / Q600 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| ● for short-circuit protection of the main circuit | |
| B10 value with high demand rate according to SN 31920 | 1 000 000 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['-', '230'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['-', '230'] |
| inductive power factor with closing power of the coil | |
| installation altitude at height above sea level maximum | 2 000 m |
| product function control circuit interface with IO link | No |
| protection class IP on the front according to IEC 60529 | IP20 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| inductive power factor with the holding power of the coil | |
| ● of the supplied function module for wye-delta circuits | 3RA2816-0EW20 |
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| ● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2014 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| operating range factor control supply voltage rated value of magnet coil at AC | |
| General Product ApprovalDeclaration of ConformityTest CertificatesMarine / ShippingConfirmationUK Declaration of ConformityType Test Certificates/Test ReportotherDangerous GoodConfirmationTransport Information | General Product Approval |