| Parameter | Value |
|---|---|
| EAN | 4011209836068 |
| UPC | 662643905137 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 97 mm |
| width | 90 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 101 mm |
| — solid | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
| ● at AC | 7,5g / 5 ms, 4,7g / 10 ms |
| ● at DC | 10g / 5 ms, 7,5g / 10 ms |
| Group Code | R711 |
| — upwards | 6 mm |
| ● at AC-3 | |
| Confirmation | |
| Date5/4/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | LCO----- |
| — forwards | 6 mm |
| ● at 50 Hz | 0.8 ... 1.1 |
| ● at 60 Hz | 0.8 ... 1.1 |
| Product Group | 5337 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 6 mm |
| Commodity Code | 85364900 |
| Product family | SIRIUS 3RA23 reversing contactor assemblies, up to 55 kW |
| last modified: | 2/8/2022 |
| Net Weight (kg) | 0,885 Kg |
| operating power | |
| — at the side | 6 mm |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| required spacing | |
| Country of origin | Germany |
| Marine / Shipping | other |
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| size of contactor | S0 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| ● for live parts | |
| ● of magnet coil | Screw-type terminals |
| Function (EF000030) | Reversing contactor |
| Packaging Dimension | 97,00 x 109,00 x 112,00 |
| Product Description | Reversing contactor assembly AC-3,5,5 kW/400 V,AC24V,50/60Hz 3-pole, Size S0 screw terminal electrical and mechanical interlock |
| ambient temperature | |
| product designation | Reversing contactor assembly |
| ● during operation | -25 ... +60 °C |
| — solid or stranded | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
| ● for main contacts | |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM300:Active Product |
| design of the fuse link | |
| General Product Approval | Declaration of Conformity |
| product type designation | 3RA23 |
| — at 400 V rated value | 5.5 kW |
| — at 500 V rated value | 5.5 kW |
| — at 690 V rated value | 7.5 kW |
| ● at 400 V rated value | 12 A |
| ● at 480 V rated value | 11 A |
| ● at 50 Hz rated value | 24 V |
| ● at 500 V rated value | 12 A |
| ● at 60 Hz rated value | 24 V |
| ● at 600 V rated value | 11 A |
| ● at 690 V rated value | 9 A |
| ● of contactor typical | 10 000 000 |
| ● instantaneous contact | 2 |
| Export Control Regulations | AL : N / ECCN : N |
| ● for auxiliary contacts | |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| operational current at AC-3 | |
| Package size unit of measure | MM |
| ● at 220/230 V rated value | 3 hp |
| ● at 460/480 V rated value | 7.5 hp |
| ● at 575/600 V rated value | 10 hp |
| ● for main current circuit | screw-type terminals |
| Substance Prohibitance (Date) | 10/01/2009 |
| manufacturer's article number | |
| type of electrical connection | |
| ● per direction of rotation | 1 |
| control supply voltage 1 at AC | |
| ● with side-by-side mounting | |
| ● 1 of the supplied contactor | 3RT2024-1AC20 |
| ● 2 of the supplied contactor | 3RT2024-1AC20 |
| proportion of dangerous failures | |
| shock resistance with sine pulse | |
| ● at AC-4 at 400 V rated value | 5.5 kW |
| product extension auxiliary switch | Yes |
| product function bus communication | Yes |
| operating frequency at AC-3 maximum | 1 000 1/h |
| ● at AWG cables for main contacts | 2x (16 ... 12), 2x (14 ... 8) |
| ● of the supplied RH assembly kit | 3RA2923-2AA1 |
| Degree of protection (IP) (EF005474) | IP20 |
| Article Number (Market Facing Number) | 3RA2324-8XB30-1AC2 |
| Rated operation power NEMA (EF011960) | 5.516240625 |
| Voltage type for actuating (EF008242) | AC |
| ● for auxiliary and control circuit | screw-type terminals |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| — with type of assignment 2 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 25 A |
| number of NC contacts for main contacts | 0 |
| number of NO contacts for main contacts | 3 |
| reference code according to IEC 81346-2 | Q |
| shock resistance at rectangular impulse | |
| ● at contactor for auxiliary contacts | Screw-type terminals |
| number of poles for main current circuit | 3 |
| — with type of coordination 1 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 63 A |
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
| contact reliability of auxiliary contacts | < 1 error per 100 million operating cycles |
| mechanical service life (switching cycles) | |
| apparent holding power of magnet coil at AC | |
| apparent pick-up power of magnet coil at AC | |
| protocol is supported AS-Interface protocol | No |
| full-load current (FLA) for 3-phase AC motor | |
| number of NO contacts for auxiliary contacts | |
| type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm² |
| operating voltage at AC-3 rated value maximum | 690 V |
| type of voltage of the control supply voltage | AC |
| ● with low demand rate according to SN 31920 | 40 % |
| Rated operation power at AC-3, 400 V (EF001364) | 5.5 |
| ● with high demand rate according to SN 31920 | 75 % |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 12 |
| Region Specific PriceGroup / Headquarter Price Group | 41B / 41B |
| contact rating of auxiliary contacts according to UL | A600 / Q600 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| ● for short-circuit protection of the main circuit | |
| B10 value with high demand rate according to SN 31920 | 1 000 000 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['-', '24'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['-', '24'] |
| inductive power factor with closing power of the coil | |
| installation altitude at height above sea level maximum | 2 000 m |
| product function control circuit interface with IO link | No |
| protection class IP on the front according to IEC 60529 | IP20 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| yielded mechanical performance [hp] for 3-phase AC motor | |
| inductive power factor with the holding power of the coil | |
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| ● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2009 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| operating range factor control supply voltage rated value of magnet coil at AC | |
| General Product ApprovalDeclaration of ConformityTest CertificatesConfirmationUK Declaration of ConformitySpecial Test CertificateMarine / ShippingMarine / ShippingotherRailwayConfirmationVibration and Shock | General Product Approval |
Technical specifications and performance data
Installation and operation guide