| Parameter | Value |
|---|---|
| Value | |
| EAN | 4011209550612 |
| UPC | Not available |
| Depth | 173 mm |
| Notes | Product is no longer availableSucessor:SIRIUS Innovation 3RA2If you need assistance please contact our local Siemens office |
| Width | 55 mm |
| Height | 295 mm |
| — solid | 0.7 ... 35 mm², 2x (0.75 ... 25 mm²) |
| Group Code | R711 |
| Price Group | 41D |
| — upwards | 50 mm |
| ● at AC-3 | |
| ● maximum | 2 000 m |
| Metal Factor | LCO----- |
| — forwards | 10 mm |
| — stranded | 0.7 ... 35 mm², 2x (0.75 ... 25 mm²) |
| ● stranded | 0.7 ... 35 mm² |
| Mounting type | snap-on fastening on 35 mm standard rail |
| Product Group | 3709 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| — Backwards | 0 mm |
| — downwards | 0 mm |
| Commodity Code | 85364900 |
| Product family | Not available |
| last modified: | 08/13/2020 |
| Net Weight (kg) | 2,105 Kg |
| Operating power | |
| — at the side | 0 mm |
| Depth (EF000049) | 173.0 |
| Required spacing | |
| Shock resistance | 8g |
| Width (EF000008) | 55.0 |
| Country of origin | Germany |
| Height (EF000040) | 295.0 |
| Marine / Shipping | other |
| Operating current | |
| Operating voltage | |
| Product extension | |
| ● 1 rated value | 50 Hz |
| LKZ_FDB/ CatalogID | CC-IC10 |
| PLM Effective Date | Product discontinued since: 01.04.2020 |
| Packaging Quantity | 1 |
| Type of assignment | 2 |
| product brand name | SIRIUS |
| ● during storage | -55 ... +80 °C |
| ● for live parts | |
| Ambient temperature | |
| Degree of pollution | 3 |
| Packaging Dimension | 65,00 x 302,00 x 192,00 |
| Product Description | Load feeder fuseless direct-on-line starting, 400 V AC 36...45 A, 24 V AC 50 Hz Size S2 Screw terminal on adapter Screw and snap-on mounting Type of coordination 2, Iq = 50 kA (also fulfills type of coordination 1) !!! Phased-out product !!! Successor is SIRIUS 3RA2 |
| Product designation | non-fused load feeder |
| Size of load feeder | S2 |
| With fuse (EF006693) | false |
| ● Auxiliary switch | Yes |
| ● during operation | -20 ... +70 °C |
| Design of the product | direct starter |
| Number of CO contacts | |
| Protocol is supported | |
| ● for main contacts | |
| ● mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM490:Start of final year of support |
| General Product Approval | For use in hazardous locations |
| Release class (EF006668) | - |
| — at 400 V rated value | 41 A |
| ● at 400 V rated value | 50 kA |
| ● at 50 Hz rated value | 24 V |
| ● of contactor typical | 10 000 000 |
| ● AS-Interface protocol | No |
| Export Control Regulations | ECCN : N / AL : N |
| ● for auxiliary contacts | 0 |
| No-load switching frequency | 15 1/s |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| With transformer (EF000278) | false |
| Package size unit of measure | MM |
| Type of the motor protection | bimetal |
| ● number of digital inputs | 0 |
| ● single or multi-stranded | 0.7 ... 35 mm² |
| Manufacturer's article number | |
| ● of the supplied contactor | 3RT1036-1AB00 |
| Control supply voltage 1 at AC | |
| Product Dimensions (W x L x H) | Not available |
| ● certificate of suitability | UL / CSA / CCC / GL / LRS / BV / DNV / PRS |
| ● with side-by-side mounting | |
| design of the switching contact | electromechanical |
| ● at AC-3 rated value maximum | 400 V |
| ● of the supplied link module | 3RA1931-1AA00 |
| Type of motor starter (EF009598) | Direct online starter (DOL) |
| control supply voltage frequency | |
| Rail mounting possible (EF003972) | - |
| Design of short-circuit protection | circuit-breakers |
| External reset possible (EF003426) | - |
| product function bus communication | No |
| ● Insulation voltage rated value | 690 V |
| Degree of protection (IP) (EF005474) | IP20 |
| Surge voltage resistance rated value | 6 kV |
| ● of the supplied circuit-breakers | 3RV1031-4GA10 |
| ● protection class IP on the front | IP20 |
| Article Number (Market Facing Number) | 3RA1130-4GB36-0AB0 |
| Number of indicator lights (EF001965) | 0 |
| Rated operation current Ie (EF001443) | 41 |
| Reference code acc. to DIN EN 81346-2 | Q |
| Voltage type for actuating (EF008242) | AC / #NO_DATA# |
| With short-circuit release (EF006691) | true |
| Degree of protection (NEMA) (EF011959) | - |
| Number of command positions (EF001372) | - |
| Suitable for emergency stop (EF001433) | - |
| Supporting protocol for ASI (EF003051) | false |
| Supporting protocol for CAN (EF003053) | - |
| Supporting protocol for LON (EF003017) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ● at AWG conductors for main contacts | 2x (30 ... 2) |
| Number of poles for main current circuit | 3 |
| Supporting protocol for Modbus (EF003057) | - |
| Supporting protocol for SERCOS (EF006657) | - |
| Supporting protocol for TCP/IP (EF003050) | - |
| product function short circuit protection | Yes |
| Mechanical service life (switching cycles) | |
| Supporting protocol for SUCONET (EF003060) | - |
| Overload release current setting (EF002336) | ['36', '45'] |
| Supporting protocol for INTERBUS (EF003054) | - |
| Supporting protocol for PROFIBUS (EF003052) | - |
| ● protocol is supported PROFINET protocol | No |
| Number of NC contacts for auxiliary contacts | 0 |
| Number of NO contacts for auxiliary contacts | 0 |
| Supporting protocol for DeviceNet (EF003059) | - |
| Supporting protocol for PROFIsafe (EF007526) | - |
| Type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 0.75 ... 25 mm², 2x (0.75 ... 16 mm²) |
| ● finely stranded with core end processing | 0.75 ... 25 mm² |
| Rated power, 460 V, 60 Hz, 3-phase (EF009600) | - |
| Rated power, 575 V, 60 Hz, 3-phase (EF009601) | - |
| Type of voltage of the control supply voltage | AC |
| Supporting protocol for EtherNet/IP (EF007521) | - |
| Supporting protocol for PROFINET IO (EF007525) | - |
| Supporting protocol for SafetyBUS p (EF007527) | - |
| ● protocol is supported PROFIBUS DP protocol | No |
| Installation altitude at height above sea level | |
| Rated operation power at AC-3, 400 V (EF001364) | 22.0 |
| Supporting protocol for Data-Highway (EF003058) | - |
| Supporting protocol for PROFINET CBA (EF007524) | - |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| Rated operation current at AC-3, 400 V (EF009602) | 41 |
| Supporting protocol for INTERBUS-Safety (EF006662) | - |
| ● of the supplied standard mounting rail adapter | 3RA1932-1AA00 |
| Supporting protocol for DeviceNet Safety (EF007520) | - |
| Supporting protocol for other bus systems (EF003062) | - |
| Ambient temperature, upper operating limit (EF009603) | - |
| Connectable conductor cross-section for main contacts | |
| Maximum short-circuit current breaking capacity (Icu) | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| Supporting protocol for Foundation Fieldbus (EF007522) | - |
| Temperature compensated overload protection (EF009604) | - |
| AWG number as coded connectable conductor cross section | |
| Coordination class according to IEC 60947-4-3 (EF012390) | Class 2 |
| Rated operation power at AC-3, 230 V, 3-phase (EF009599) | - |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| ● Type of electrical connection for main current circuit | screw-type terminals |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | - |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Rated conditional short-circuit current, type 2, 230 V (EF009606) | - |
| Rated conditional short-circuit current, type 2, 400 V (EF009605) | - |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 |
| Rated conditional short-circuit current, type 1, 480 Y/277 V (EF009607) | - |
| Rated conditional short-circuit current, type 1, 600 Y/347 V (EF009608) | - |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| adjustable pick-up value current of the current-dependent overload release | 36 ... 45 A |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | - |
| General Product ApprovalFor use in hazardous locationsDeclaration of ConformityMarine / ShippingMiscellaneousMarine / ShippingotherConfirmation | General Product Approval |
Technical specifications and performance data