Service time: Monday to Friday 9:00-18:00
3LD2017-0TK11 - 3LD2017-0TK11 SIEMENS SENTRON, switch disconnector 3LD, main switch, 3-pole, Iu: 16 A, operating power / at ..
In Stock Hot Product

3LD2017-0TK11

3LD2017-0TK11 SIEMENS SENTRON, switch disconnector 3LD, main switch, 3-pole, Iu: 16 A, operating power / at ..

$0.00USD
3048 in stock
Key Specifications
:
EAN:4011209718555
UPC:754554968575
ETIM:5
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
EAN4011209718555
UPC754554968575
ETIM5
depth385 mm
width67 mm
UNSPSC14
eClass6
height75 mm
● solid1x (1...6mm²)
Group CodeP360
net weight419 g
● maximum10
● minimum18
Date5/5/2022
Metal FactorLAO-----
● stranded1x (1..6mm²)
Product Group5887
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Quantity Unit1 Piece
Commodity Code85365080
Product familyBasic Devices
power loss [W]
type of devicefixed mounting
type of switchFloor mounting with door coupling
Net Weight (kg)0,420 Kg
number of poles3
operating power
product feature
● main switchYes
● motor driveNo
design of handleknob-operated mechanism, black
fastening methodBuilt-in unit fixed-mounted version
Country of originGermany
● rail mountingYes
● safety switchYes
LKZ_FDB/ CatalogIDLV10.1
Packaging Quantity1
product brand nameSENTRON
Packaging Dimension85,00 x 462,00 x 70,00
Product DescriptionSENTRON, switch disconnector 3LD, main switch, 3-pole, Iu: 16 A, operating power / at AC-23 A at 400 V: 7.5 kW, floor mounting with door coupling, defeatable knob-operated mechanism, black, 4-hole mounting of the handle
operational current
product designation3LD Switch disconnector
protection class IPIP65
suitability for use
● voltage triggerNo
design of the productMain switch
Product Lifecycle (PLM)PM300:Active Product
design of the fuse link
● at AC / rated value16 A
● switch disconnectorYes
General Product ApprovalDeclaration of Conformity
Interlockable (EF006281)true
● EMERGENCY OFF switchNo
● 4-hole front mountingYes
● at AC-23 A / at 690 V6 000
Export Control RegulationsAL : N / ECCN : N
Number of poles (EF001391)3
● for auxiliary contactsconnection terminals
Standard lead time ex-works80 Day/Days
Surcharge for Raw MaterialsNone
size of switch disconnector1
● at 40 °C / rated value16 A
● at 45 °C / rated value16 A
● at 50 °C / rated value16 A
● at 55 °C / rated value16 A
● per conductor / typical1 W
Package size unit of measureMM
product extension / optional
● for main current circuitbox terminal
Number of switches (EF005586)1
operating frequency / maximum50 1/h
type of electrical connection
● maintenance/repair switchYes
Device construction (EF008240)Built-in device fixed built-in technique
type of fuse / according to ULRK5
Motor drive optional (EF007386)false
design of the actuating elementselector switch
color / of the actuating elementblack
degree of protection NEMA rating1, 3R, 4X, 12
insulation voltage / rated value690 V
Colour control element (EF007167)Black
Motor drive integrated (EF006697)false
Version as main switch (EF006981)true
number of bracket locks / maximum3
operational current / rated value16 A
Rated operating voltage (EF001435)-
Type of control element (EF006976)Toggle
protection class IP / on the frontIP65
Switching power at 400 V (EF009166)-
Version as safety switch (EF006985)true
Voltage release optional (EF007491)false
● can be locked into OFF positionYes
● at AC-3 / at 240 V / rated value3 kW
● at AC-3 / at 400 V / rated value6 kW
● at AC-3 / at 690 V / rated value5.5 kW
Article Number (Market Facing Number)3LD2017-0TK11
Rated permanent current Iu (EF001389)16.0
● at AC-21 / at 690 V / rated value16 A
Degree of protection (NEMA) (EF011959)-
Suitable for floor mounting (EF007243)FALSE
Version as reversing switch (EF009408)false
WEEE (2012/19/EU) Take-Back ObligationYes
ambient temperature / during operation
surge voltage resistance / rated value6 kV
electrical endurance (switching cycles)
● at 690 V / by gG fuse / rated value50 kA
● at AC-21 A / at 240 V / rated value16 A
● at AC-21 A / at 440 V / rated value16 A
● at AC-23 A / at 240 V / rated value4 kW
● at AC-23 A / at 400 V / rated value16 A
● at AC-23 A / at 440 V / rated value7.5 kW
● at AC-23 A / at 690 V / rated value8 kW
let-through current / with closed switch
● front mounting with central attachmentNo
type of the driving mechanism / motor driveNo
Max. rated operation voltage Ue AC (EF007355)690
Suitable for front mounting 4-hole (EF007247)true
Suitable for front mounting centre (EF007248)false
Suitable for intermediate mounting (EF007264)true
ambient temperature / during storage / minimum-25 °C
number of CO contacts / for auxiliary contacts0
number of NC contacts / for auxiliary contacts0
number of NO contacts / for auxiliary contacts0
● finely stranded / with core end processing1x (1...4mm²)
Rated operation power at AC-3, 400 V (EF001364)5.5
hasp thickness / of the bracket locks / maximum6 mm
hasp thickness / of the bracket locks / minimum4 mm
Degree of protection (IP), front side (EF003118)IP65
Rated operation power at AC-23, 400 V (EF007027)0.0075
Rated short-time withstand current lcw (EF007050)0.34
Version as emergency stop installation (EF006959)false
Version as maintenance-/service switch (EF006986)true
Rated permanent current at AC-21, 400 V (EF009165)16
Rated permanent current at AC-23, 400 V (EF011777)-
Region Specific PriceGroup / Headquarter Price Group12R / 1CL
mechanical service life (switching cycles) / typical100 000
operational current / of upstream fuse / rated value20 A
Conditioned rated short-circuit current Iq (EF001444)-
Suitable for distribution board installation (EF007262)true
Type of electrical connection of main circuit (EF006819)Frame clamp
● at 440 V / for combination switch + gG fuse / maximum3 kA
insulation voltage / of the auxiliary switch / rated value500 V
continuous current / of the auxiliary contact / rated value10 A
operating voltage / of auxiliary contacts / at AC / maximum500 V
Number of auxiliary contacts as change-over contact (EF003531)0
● for short-circuit protection of the main circuit / requiredfuse gL/gG: 20 A
Number of auxiliary contacts as normally open contact (EF001376)0
display version / for switch position indicator manual operation1 ON - 0 OFF
AWG number / as coded connectable conductor cross section / solid
Number of auxiliary contacts as normally closed contact (EF001377)0
conditional short-circuit current / with line-side fuse protection
type of connectable conductor cross-sections / for copper conductor
● for short-circuit protection of the auxiliary switch / requiredfuse gL/gG: 10 A
continuous current / of upstream fuse / according to UL / rated value50 A
type of connectable conductor cross-sections / for auxiliary contacts
● at 690 V / for combination switch + gG fuse / maximum permissible3 kA
Compliance with the substance restrictions according to RoHS directiveSince: 15.03.2005
REACH Art. 33 Duty to inform according to the current list of candidatesReach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
operational current / at AC / according to UL 508/UL 60947-4-1 / rated value16 A
● for rated value of the current / at AC / in hot operating state / per pole0.5 W
number of connectable CO contacts / for auxiliary contacts / attachable / maximum0
number of connectable NC contacts / for auxiliary contacts / attachable / maximum3
number of connectable NO contacts / for auxiliary contacts / attachable / maximum5
short-time withstand current (SCCR) / at 600 V / according to UL 508/UL 60947-4-15 kA
active power [hp] / at AC / at 480 V / according to UL 508/UL 60947-4-1 / rated value7.5
active power [hp] / at AC / at 600 V / according to UL 508/UL 60947-4-1 / rated value10
I2t value / with closed switch / at 690 V / for combination switch + gG fuse / maximum3 kA2.s
operating voltage / at AC / at 50/60 Hz / according to UL 508/UL 60947-4-1 / rated value600 V
let-through I2t value / with closed switch / at 440 V / for combination switch + gG fuse / maximum2.5 kA2.s
General Product ApprovalConfirmationMiscellaneousGeneral Product ApprovalDeclaration of ConformityMarine / ShippingotherUK Declaration of ConformityMiscellaneousEnvironmental ConfirmationsGeneral Product Approval

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top