| Parameter | Value |
|---|---|
| Value | |
| EAN | 4011209739178 |
| UPC | Not available |
| ETIM | 4 |
| Depth | 143 mm |
| Notes | Sucessor:3KF1406-0MB11, different dimensions, some deviating technical values. |
| Width | 215 mm |
| Height | 106 mm |
| UNSPSC | 14 |
| eClass | 6 |
| version | Complete version with rotary operating mechanism |
| ● 400V | 100 kA |
| ● 500V | 100 kA |
| Group Code | P360 |
| Design type | For mounting and installation |
| Fuse system | fuses according to BS 88 |
| Price Group | 12S |
| ● maximum | 55 °C |
| ● minimum | -25 °C |
| Metal Factor | LAO----- |
| Mounting type | Surface mounting and installation |
| Product Group | 5853 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85362010 |
| Product family | Not available |
| Net Weight (kg) | 2,529 Kg |
| Operating power | |
| number of poles | 4 |
| type of voltage | AC/DC |
| Type of mounting | fixed mounted |
| Country of origin | Germany |
| Operating voltage | |
| mounting position | any |
| LKZ_FDB/ CatalogID | LV10.1 |
| PLM Effective Date | Product phase-out since: 31.08.2018 |
| Packaging Quantity | 1 |
| product brand name | SENTRON |
| Packaging Dimension | 183,00 x 268,00 x 199,00 |
| Product Description | Switch disconnector with fuse in new design Iu=63 A, Ue = 690 V, 4-pole for BS88 fuse form A2/A3 4th pole selectable, without Fuse with door operating mechanism 8UC7 Handle dark blue/blue-green Basic masking frame light gray |
| Product designation | Switch disconnector |
| Protection class IP | IP00 |
| Design of the product | With 3KL fuses |
| ● AC-21 A / at 400 V | 63 A |
| ● AC-21 A / at 500 V | 63 A |
| ● AC-21 B / at 400 V | 63 A |
| ● AC-21 B / at 500 V | 63 A |
| ● AC-22 A / at 400 V | 63 A |
| ● AC-22 A / at 500 V | 63 A |
| ● AC-22 B / at 400 V | 63 A |
| ● AC-22 B / at 500 V | 63 A |
| ● stranded / maximum | 35 mm² |
| Product Lifecycle (PLM) | PM400:Phase Out Started |
| ● at DC / rated value | 440 V |
| Interlockable (EF006281) | true |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | AL : N / ECCN : N |
| Number of poles (EF001391) | 4 |
| Size of disconnecting link | Form A2/A3 |
| certificate of suitability | CE |
| Product feature / interlock | Yes |
| Standard lead time ex-works | 15 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| Number of switches (EF005586) | - |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Product Dimensions (W x L x H) | Not available |
| Motor drive optional (EF007386) | false |
| Operating current / rated value | 63 A |
| Continuous current / rated value | 63 A |
| Insulation voltage / rated value | 690 V |
| Type of connection, main circuit | flat pad connection, M6 |
| Colour control element (EF007167) | - |
| Design of the operating mechanism | manual operating mechanism |
| Motor drive integrated (EF006697) | false |
| Version as main switch (EF006981) | true |
| ● mounting type / rail mounting | No |
| Rated operating voltage (EF001435) | - |
| Type of control element (EF006976) | Other |
| Switching power at 400 V (EF009166) | - |
| Version as safety switch (EF006985) | true |
| Voltage release optional (EF007491) | false |
| Ambient temperature / during storage | |
| Article Number (Market Facing Number) | 3KL5040-1GG01 |
| Rated permanent current Iu (EF001389) | 63.0 |
| ● at AC / at 50/60 Hz / rated value | 690 V |
| Ambient temperature / during operation | |
| Degree of protection (NEMA) (EF011959) | - |
| Design of the load switch / Strip form | No |
| Suitable for floor mounting (EF007243) | FALSE |
| Surge voltage resistance / rated value | 6 000 V |
| Version as reversing switch (EF009408) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Conditional rated short-circuit current | |
| ● at AC-23 A / at 500 V / rated value | 30 000 W |
| Number of poles / for main current circuit | 4 |
| Operating current / at AC-21 / rated value | 63 A |
| Type of the driving mechanism / motor drive | No |
| ● reference code / acc. to DIN EN 61346-2 | Q |
| Max. rated operation voltage Ue AC (EF007355) | 690 |
| Suitable for front mounting 4-hole (EF007247) | false |
| Suitable for front mounting centre (EF007248) | false |
| Suitable for intermediate mounting (EF007264) | false |
| Number of CO contacts / for auxiliary contacts | 0 |
| Number of NC contacts / for auxiliary contacts | 0 |
| Number of NO contacts / for auxiliary contacts | 0 |
| Rated operation power at AC-3, 400 V (EF001364) | - |
| Degree of protection (IP), front side (EF003118) | IP00 |
| Rated operation power at AC-23, 400 V (EF007027) | 30.0 |
| ● in utilization category / AC-21 A / at 400 V | 100 kA |
| ● in utilization category / AC-21 A / at 500 V | 100 kA |
| ● in utilization category / AC-21 B / at 400 V | 100 kA |
| ● in utilization category / AC-21 B / at 500 V | 100 kA |
| ● in utilization category / AC-22 A / at 400 V | 100 kA |
| ● in utilization category / AC-22 A / at 500 V | 100 kA |
| ● in utilization category / AC-22 B / at 400 V | 100 kA |
| ● in utilization category / AC-22 B / at 500 V | 100 kA |
| Rated short-time withstand current lcw (EF007050) | - |
| Version as emergency stop installation (EF006959) | false |
| Version as maintenance-/service switch (EF006986) | true |
| Rated permanent current at AC-21, 400 V (EF009165) | - |
| Rated permanent current at AC-23, 400 V (EF011777) | 63 |
| Rated current Ie / maximum / in utilization category | |
| Conditioned rated short-circuit current Iq (EF001444) | - |
| ● at AC-23 A / at 400 V / at 50/60 Hz / rated value | 30 000 W |
| ● at AC-23 A / at 690 V / at 50/60 Hz / rated value | 40 000 W |
| Connectable conductor cross-section / for main contacts | |
| Suitable for distribution board installation (EF007262) | false |
| Type of electrical connection of main circuit (EF006819) | Other |
| ● Mounting type / front mounting with 4-hole attachment | No |
| ● Mounting type / front mounting with central attachment | No |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.06.2007 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 2.83 W |
| Let-through current / I2 t / maximum permissible / in utilization category / AC-22 B / at 400 V | 55 000 A²·s |
| Declaration of ConformityTest CertificatesShipping ApprovalotherSpecial Test CertificateEnvironmental Confirmations | Declaration of Conformity |