| Parameter | Value |
|---|---|
| EAN | 4001869515120 |
| UPC | Not available |
| ETIM | 5 |
| depth | 68 mm |
| width | 202 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 126 mm |
| ● solid | 1x (2.5 ... 16 mm²) |
| Group Code | P360 |
| net weight | 1 777 g |
| ● maximum | 70 °C |
| ● minimum | -25 °C |
| Confirmation | |
| Metal Factor | LOA----- |
| ● stranded | 1x (10 ... 70 mm²) |
| Date5/16/2022 | |
| Product Group | 5378 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85353010 |
| Product family | Basic Devices |
| power loss [W] | |
| type of device | fixed mounting |
| Net Weight (kg) | 1,978 Kg |
| number of poles | 6 |
| ● main switch | Yes |
| ● motor drive | No |
| fastening method | Screw fixing and standard rail mounting 35 mm |
| ● on the front | IP20 |
| Country of origin | China |
| Marine / Shipping | other |
| mounting position | any |
| product component | |
| ● rail mounting | Yes |
| ● safety switch | Yes |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| insulation voltage | |
| product brand name | SENTRON |
| ● trip indicator | No |
| Packaging Dimension | 202,00 x 68,00 x 126,00 |
| Product Description | Switch disconnector 125 A, Size 2, 6-pole DC Front operating mechanism center Basic unit without handle Box terminal |
| operational current | |
| product designation | 3KD switch disconnector |
| protection class IP | IP20 |
| suitability for use | |
| ● voltage trigger | No |
| overvoltage category | III |
| design of the product | DC switch |
| ● for copper busbar | '1 x (3 x 14 mm²) |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● switch disconnector | Yes |
| General Product Approval | Declaration of Conformity |
| Interlockable (EF006281) | false |
| ● EMERGENCY OFF switch | Yes |
| ● undervoltage release | No |
| ● 4-hole front mounting | No |
| Export Control Regulations | AL : N / ECCN : N |
| Number of poles (EF001391) | 6 |
| ● at DC-21 A / at 1000 V | 1 500 |
| Standard lead time ex-works | 5 Day/Days |
| Surcharge for Raw Materials | None |
| product feature / interlock | No |
| size of switch disconnector | 2 |
| ● at 40 °C / rated value | 125 A |
| ● at 45 °C / rated value | 125 A |
| ● at 50 °C / rated value | 125 A |
| ● at 55 °C / rated value | 125 A |
| ● at 60 °C / rated value | 125 A |
| ● at 65 °C / rated value | 125 A |
| ● at 70 °C / rated value | 125 A |
| Package size unit of measure | MM |
| product extension / optional | |
| Number of switches (EF005586) | - |
| type of the driving mechanism | Front operating mechanism |
| ● maintenance/repair switch | Yes |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Motor drive optional (EF007386) | false |
| design of the actuating element | Without handle |
| Colour control element (EF007167) | Other |
| Motor drive integrated (EF006697) | false |
| Version as main switch (EF006981) | true |
| operational current / rated value | 125 A |
| Rated operating voltage (EF001435) | - |
| Type of control element (EF006976) | None |
| short-time withstand current (Icw) | |
| Switching power at 400 V (EF009166) | - |
| Version as safety switch (EF006985) | true |
| Voltage release optional (EF007491) | false |
| ambient temperature / during storage | |
| product extension / auxiliary switch | Yes |
| Article Number (Market Facing Number) | 3KD3260-2NE20-0 |
| Rated permanent current Iu (EF001389) | 125.0 |
| Degree of protection (NEMA) (EF011959) | - |
| Suitable for floor mounting (EF007243) | FALSE |
| Version as reversing switch (EF009408) | false |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ambient temperature / during operation | |
| surge voltage resistance / rated value | 8 kV |
| electrical endurance (switching cycles) | |
| operational current / at DC / rated value | 125 A |
| ● front mounting with central attachment | No |
| type of the driving mechanism / motor drive | No |
| position / of the switch operating mechanism | after the third pole |
| type of connectable conductor cross-sections | |
| Max. rated operation voltage Ue AC (EF007355) | - |
| Suitable for front mounting 4-hole (EF007247) | false |
| Suitable for front mounting centre (EF007248) | false |
| Suitable for intermediate mounting (EF007264) | true |
| ● undervoltage release with leading contact | No |
| number of CO contacts / for auxiliary contacts | 4 |
| number of NC contacts / for auxiliary contacts | 0 |
| number of NO contacts / for auxiliary contacts | 0 |
| ● finely stranded / with core end processing | 1x (2.5 ... 70 mm²) |
| Rated operation power at AC-3, 400 V (EF001364) | - |
| Degree of protection (IP), front side (EF003118) | IP20 |
| Rated operation power at AC-23, 400 V (EF007027) | - |
| operating voltage / with current paths in series | |
| Rated short-time withstand current lcw (EF007050) | - |
| Version as emergency stop installation (EF006959) | true |
| Version as maintenance-/service switch (EF006986) | true |
| Rated permanent current at AC-21, 400 V (EF009165) | - |
| Rated permanent current at AC-23, 400 V (EF011777) | - |
| ● at DC-21 A / at 1200 V / rated value / maximum | 125 A / 6 |
| Region Specific PriceGroup / Headquarter Price Group | 12S / 1CL |
| mechanical service life (switching cycles) / typical | 15 000 |
| ● at DC / at 1200 V / limited to 1 s / rated value | 4 kA |
| ● with degree of pollution 2 / at DC / rated value | 1200 V / 6 |
| ● with degree of pollution 3 / at DC / rated value | 1000 V / 6 |
| Conditioned rated short-circuit current Iq (EF001444) | - |
| ● with closed switch / with cover or cable lug cover | IP20 |
| ● with conventional rated thermal current / per pole | 3.2 W |
| Suitable for distribution board installation (EF007262) | true |
| Type of electrical connection of main circuit (EF006819) | Frame clamp |
| number of connected CO contacts / for auxiliary contacts | 0 |
| number of connected NC contacts / for auxiliary contacts | 0 |
| number of connected NO contacts / for auxiliary contacts | 0 |
| type of electrical connection / for main current circuit | box terminal |
| ● with conventional rated thermal current / per device | 19.2 W |
| Number of auxiliary contacts as change-over contact (EF003531) | 4 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| ● at AC / at 1200 V / without fuse link / rated value / minimum | 5.7 kA |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| type of connectable conductor cross-sections / for copper conductor | |
| type of connectable conductor cross-sections / with flexible busbar | 3x (0.8x14 mm²) |
| short-circuit current making capacity (Icm) / for switch disconnector | |
| Compliance with the substance restrictions according to RoHS directive | Since: 24.11.2009 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| ● for rated value of the current / at AC / in hot operating state / per pole | 3.2 W |
| display version / for switch position indicator door-coupling rotary operating mechanism | ON-OFF |
| General Product ApprovalDeclaration of ConformityConfirmationMiscellaneousUK Declaration of ConformityMarine / ShippingotherMiscellaneous | General Product Approval |
Technical specifications and performance data
Installation and operation guide