| Parameter | Value |
|---|---|
| Remarks: (Dimensions) | Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captIIIe screw |
| Customs Tariff Number: | 85362020 |
| Minimum Order Quantity: | 1 piece |
| Standards: (Dimensions) | IEC/EN 60947-2IEC/EN 60898-1 |
| Power Loss: (Dimensions) | at Rated Operating Conditions per Pole 3.2 W |
| RoHS Status: (Technical) | Following EU Directive 2011/65/EU |
| Terminal Type: (Dimensions) | Screw Terminals |
| Number of Poles: (Dimensions) | 4 |
| Housing Material: (Dimensions) | Insulation group I, RAL 7035 |
| Pollution Degree: (Dimensions) | 3 |
| ETIM 4: (Container Information) | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 5: (Container Information) | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 6: (Container Information) | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 7: (Container Information) | EC000042 - Miniature circuit breaker (MCB) |
| Mounting Position: (Dimensions) | Any |
| Tightening Torque: (Dimensions) | 3.5 N·m |
| Rated Current (In): (Dimensions) | 32 A |
| Connecting Capacity: (Dimensions) | Flexible 1 ... 50 mm²Stranded 1 ... 70 mm² |
| Rated Frequency (f): (Dimensions) | 50 / 60 Hz |
| RoHS Information: (Environmental) | 2CCC413008D0206 |
| Degree of Protection: (Dimensions) | acc. to IEC 60529 IP20 |
| Mounting on DIN Rail: (Dimensions) | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Overvoltage Category: (Dimensions) | III |
| Ambient Air Temperature: (Technical) | Operation -25 ... +60 °CStorage -40 ... +70 °C |
| Instructions and Manuals: (Ordering) | 2CCC413016M0008 |
| Tripping Characteristic: (Dimensions) | D |
| Product Net Width: (Popular Downloads) | 106 mm |
| Recommended Screw Driver: (Dimensions) | Pozidriv 2 |
| Product Net Height: (Popular Downloads) | 95 mm |
| Product Net Weight: (Popular Downloads) | 980 g |
| Rated Operational Voltage: (Dimensions) | 230/400 V AC |
| Contact Position Indication: (Dimensions) | ON / OFF / TRIP |
| Instructions and Manuals: (Environmental) | 2CCC413016M0008 |
| Environmental Information: (Environmental) | 2CCY413207D0203 |
| Rated Insulation Voltage (Ui): (Dimensions) | 440 V AC |
| Data Sheet, Technical Information: (Ordering) | 2CCC413003C0208 |
| Declaration of Conformity - CE: (Environmental) | 2CCC413016D0601 |
| Product Net Depth / Length: (Popular Downloads) | 82.5 mm |
| Rated Short-Circuit Capacity (Icn): (Dimensions) | (230 / 400 V AC) 10 kA |
| Object Classification Code: (Container Information) | F |
| Rated Impulse Withstand Voltage (Uimp): (Dimensions) | 4 kV |
| Rated Service Short-Circuit Breaking Capacity (Ics): (Dimensions) | (230 / 400 V AC) 10 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): (Dimensions) | (230 / 400 V AC) 16 kA(300 V DC) 10 kA |
| Package Level 1 EAN: (Certificates and Declarations (Document Number)) | 7612271415976 |
| Package Level 1 Units: (Certificates and Declarations (Document Number)) | 1 piece |
| Package Level 1 Width: (Certificates and Declarations (Document Number)) | 105 mm |
| Package Level 2 Units: (Certificates and Declarations (Document Number)) | 1 piece |
| Package Level 1 Height: (Certificates and Declarations (Document Number)) | 99 mm |
| Package Level 2 Height: (Certificates and Declarations (Document Number)) | 0.92 mm |
| Package Level 1 Gross Weight: (Certificates and Declarations (Document Number)) | 1010 g |
| Package Level 2 Gross Weight: (Certificates and Declarations (Document Number)) | 1.1 kg |
| Package Level 1 Depth / Length: (Certificates and Declarations (Document Number)) | 111 mm |