| Parameter | Value |
|---|---|
| Customs Tariff Number: | 85044090 |
| Minimum Order Quantity: | 1 piece |
| RoHS Status: (Technical) | Following EU Directive 2011/65/EU |
| Function: (Container Information) | Switch mode power supply |
| Package Level 1 EAN: (Dimensions) | 4013614503825 |
| Standards: (Container Information) | CAN/CSA C22.2 No.107.1EN 50581IEC/EN 60950-1IEC/EN 61000-6-2IEC/EN 61000-6-3IEC/EN 61204UL 508 |
| Package Level 1 Units: (Dimensions) | 1 piece |
| Package Level 1 Width: (Dimensions) | 90 mm |
| Ambient Air Temperature: (Technical) | Operation -25 ... +70 °CStorage -40 ... +85 °C |
| Instructions and Manuals: (Ordering) | 1SVC360560M0000 |
| Package Level 1 Height: (Dimensions) | 160 mm |
| Hold-up Time: (Container Information) | (230 V AC) min. 40 ms |
| Output Power: (Container Information) | 240 W |
| Product Net Width: (Popular Downloads) | 60 mm |
| Output Current: (Container Information) | 10 A |
| Product Net Height: (Popular Downloads) | 129.4 mm |
| Product Net Weight: (Popular Downloads) | 1.07 kg |
| Number of Phases: (Container Information) | 1 |
| Pollution Degree: (Container Information) | 2 |
| Tightening Torque UL/CSA: (Environmental) | Input Circuit 4.4 in·lbOutput Circuit 4.4 in·lb |
| Mounting Position: (Container Information) | Position 1, 7 |
| Package Level 1 Gross Weight: (Dimensions) | 1.21 kg |
| Tightening Torque: (Container Information) | Auxiliary Circuit 0.5 N·mControl Circuit 0.9 N·mInput Circuit 0.5 N·mOutput Circuit 0.5 N·m |
| Rated Output Power: (Container Information) | 240 W |
| Input Voltage (Uin): (Container Information) | 85 ... 264 V AC90 ... 300 V DC |
| Package Level 1 Depth / Length: (Dimensions) | 168 mm |
| Rated Frequency (f): (Container Information) | 50 Hz60 Hz |
| Data Sheet, Technical Information: (Ordering) | 2CDC114100D0201 |
| Degree of Protection: (Container Information) | Housing IP20Terminals IP20 |
| Mounting on DIN Rail: (Container Information) | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Rated Output Current: (Container Information) | -25 °C ... +40 °C 15 A-25 °C ... +60 °C 10 A |
| Rated Output Voltage: (Container Information) | 24 V DC |
| Output Voltage (Uout): (Container Information) | 24 V DC |
| Typical Input Current: (Container Information) | (115 V AC) 2.3 A(230 V AC) 1.2 A |
| Wire Stripping Length: (Container Information) | Auxiliary Circuit 8 mmInput Circuit 8 mmOutput Circuit 8 mm |
| CB Certificate: (Electromagnetic Compatibility) | CB_DK-45679-A3-UL |
| Product Net Depth / Length: (Popular Downloads) | 136 mm |
| Rated Frequency Limits: (Container Information) | 45 ... 65 Hz |
| ABS Certificate: (Electromagnetic Compatibility) | ABS_17-HG1591548-2-PDA |
| EAC Certificate: (Electromagnetic Compatibility) | EAC_RU_C-DE.ME77.B.02550 |
| Characteristic of Output: (Container Information) | U/I characteristic curve with power reserve |
| Recommended Screw Driver: (Container Information) | Input Circuit / Output Circuit PH1Input Circuit / Output Circuit 0.8 x 4 |
| RoHS Information: (Electromagnetic Compatibility) | 1SVD982010-0002 |
| Minimum Mounting Distance: (Container Information) | Electrical Conductive Board, Horizontal 25 mmElectrical Conductive Board, Vertical 25 mmOther Device Same Type, Horizontal 25 mmOther Device Same Type, Vertical 25 mm |
| Rated Input Voltage (UIN): (Container Information) | 100 ... 240 V AC90 ... 300 V DC |
| cULus Certificate: (Electromagnetic Compatibility) | cULus508_20150522-E174460 |
| cURus Certificate: (Electromagnetic Compatibility) | cURus60950_E196145-A9-UL; cURusANSI-12-12_20160916_E317914 |
| DNV GL Certificate: (Electromagnetic Compatibility) | DNV_GL_TAA00000YB_1 |
| Output Current Maximum (Iout): (Container Information) | 15 A |
| Rated Insulation Voltage (Ui): (Container Information) | Input Circuit / Output Circuit 300 VInput Circuit / PE 300 VInput Circuit / Relay Contact 300 VOutput Circuit / PE 50 V |
| Electromagnetic Compatibility (EMC): (Technical UL/CSA) | Immunity - Class BEmission - Class B |
| Resistance to Shock acc. to IEC 60068-2-27: (Technical) | 30g / 3 shocks / 6 ms |
| Surge Immunity acc. to IEC 61000-4-5: (Technical UL/CSA) | Level 4 Line-to-Ground 4 kVLevel 4 Line-to-Line 2 kV |
| Connecting Capacity Input Circuit UL/CSA: (Environmental) | Flexible with Ferrule 20-12 AWGFlexible 20-12 AWGRigid 20-10 AWG |
| ETIM 5: (Certificates and Declarations (Document Number)) | EC002540 - DC-power supply |
| ETIM 6: (Certificates and Declarations (Document Number)) | EC002540 - DC-power supply |
| ETIM 7: (Certificates and Declarations (Document Number)) | EC002540 - DC-power supply |
| Instructions and Manuals: (Electromagnetic Compatibility) | 1SVC360560M0000 |
| UNSPSC: (Certificates and Declarations (Document Number)) | 39121004 |
| eClass: (Certificates and Declarations (Document Number)) | 7.0 27049002 |
| Connecting Capacity Input Circuit: (Container Information) | Flexible with Ferrule 0.5 ... 2.5 mm²Flexible 0.5 ... 2.5 mm²Rigid 0.5 ... 4 mm² |
| Connecting Capacity Output Circuit UL/CSA: (Environmental) | Flexible 20-12 AWGRigid 20-10 AWG |
| Connecting Capacity Output Circuit: (Container Information) | Flexible with Ferrule 0.5 ... 2.5 mm²Flexible 0.5 ... 2.5 mm²Rigid 0.5 ... 4 mm² |
| Resistance to Damp Heat acc. to IEC 60068-2-30: (Technical) | Test Db: 55°C, 2 cycles |
| Resistance to Vibrations acc. to IEC 60068-2-6: (Technical) | 10-58 Hz, ±0.15 mm; 58-150 Hz, 2g, 10 sweep cycles each axis |
| Declaration of Conformity - CE: (Electromagnetic Compatibility) | 1SVD982010-0002 |
| Rated Impulse Withstand Voltage (Uimp): (Container Information) | Input Circuit / Output Circuit 4 kVInput Circuit / PE 4 kVInput Circuit / Relay Contact 4 kVOutput Circuit / PE 0.5 kVOutput Circuit 0.5 kV |
| E-Number (Sweden): (Certificates and Declarations (Document Number)) | 5213180 |
| Conducted Disturbances Immunity acc. to IEC 61000-4-6: (Technical UL/CSA) | Level 3 10 V |
| Object Classification Code: (Certificates and Declarations (Document Number)) | T |
| Electrostatic Discharge (ESD Immunity) acc. to IEC 61000-4-2: (Technical UL/CSA) | Level 4 Air Discharge 15 kVLevel 4 Contact Discharge 8 kV |
| Radiated Electromagnetic Field Immunity acc. to IEC 61000-4-3: (Technical UL/CSA) | Level 3 10 V/m |
| Electrical Fast Transient (Burst Immunity) acc. to IEC 61000-4-4: (Technical UL/CSA) | Level 4 Power Supply Port Signal 4 kV |
Technical specifications and performance data
Installation and operation guide