| Parameter | Value |
|---|---|
| Customs Tariff Number: | 85044090 |
| Minimum Order Quantity: | 1 piece |
| Product Main Type: (Dimensions) | PSTX470 |
| Rated Frequency (f): (Dimensions) | Main Circuit 50/60 Hz |
| By-pass Signal Relay: (Dimensions) | Yes |
| Instructions and Manuals: (Ordering) | 1SFC132081M0201 |
| Instructions and Manuals: (Technical) | 1SFC132081M0201 |
| Environmental Information: (Technical) | 2CMT005232 |
| Product Net Width: (Popular Downloads) | 361 mm |
| Product Net Height: (Popular Downloads) | 493 mm |
| Product Net Weight: (Popular Downloads) | 25 kg |
| Rated Operational Voltage: (Dimensions) | Main Circuit 208 ... 600 V AC |
| Initial Voltage During Start: (Dimensions) | 10 ... 99 % |
| Declaration of Conformity - CE: (Technical) | 2CMT005209 |
| Integrated Electronic Overload: (Dimensions) | Yes |
| Data Sheet, Technical Information: (Ordering) | 1SFC132009C0201 |
| Connecting Capacity Main Circuit: (Dimensions) | Hole Diameter 8.5 mm |
| Adjustable Rated Motor Current Ie: (Dimensions) | 30 ... 100 % |
| Product Net Depth / Length: (Popular Downloads) | 282 mm |
| Rated Control Supply Voltage (Us): (Dimensions) | 100 ... 250 V |
| Rated Control Circuit Voltage (Uc): (Dimensions) | DC Operation 24 V |
| Connecting Capacity Control Circuit: (Dimensions) | Rigid 1x2.5 mm² |
| E-nummer: (Certificates and Declarations (Document Number)) | 3302234 |
| Rated Operational Power - In-Line Connection (Pe): (Dimensions) | (400 V) 250 kW |
| Rated Operational Power - Inside Delta Connection: (Dimensions) | at 400 V 450 kW |
| Rated Operational Current - In-Line Connection (Ie): (Dimensions) | 470 A |
| Rated Operational Current - Inside Delta Connection: (Dimensions) | 814 A |