| Parameter | Value |
|---|---|
| India (IN) | |
| ETIM 7 | EC000216 - Switch disconnector |
| ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| eClass | V11.1 : 27371403 |
| Standards | IEC 60947-1, -3 |
| Power Loss | at Rated Operating Conditions per Pole 30...32 W |
| Handle Type | Handle and shaft not included |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Utilization | Photovoltaic |
| Mounting Type | Base Mounting |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Operating Mode | Front Operated |
| Shaft Diameter | 12 mm |
| Terminal Width | 30 mm |
| Wiring Diagram | 1SCC301046K0201 |
| CCC Certificate | CQC2019010302206498 |
| Number of Poles | 4 |
| ABB EcoSolutions | Yes |
| RoHS Information | 1SCC301239D0201 |
| Country of Origin | Finland (FI) |
| Product Net Width | 255.5 mm |
| REACH Declaration | 1SCC301240D0201 |
| Special Functions | No |
| DNV GL Certificate | 1SCC301231D0201 |
| Number of Circuits | 1 |
| Product Frame Size | M |
| Product Net Height | 211 mm |
| Product Net Weight | 9.7 kg |
| Mechanical Drawings | OTDC800...1000_F_22_OTDCKIT800FS11.igs |
| Package Level 1 EAN | 6417019913902 |
| Utilization Category | Switching of resistive loads, including moderate overloads - occasional actuation (DC-21B) |
| Customs Tariff Number | 85353010 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 270 mm |
| Minimum Order Quantity | 1 piece |
| Package Level 1 Height | 200 mm |
| Connection Configuration | Single circuit 6c, 6g |
| End of Life Instructions | 1SCC301112M0201 |
| Instructions and Manuals | 1SCC301102M0201 |
| Rated Operational Voltage | 1500 V |
| Object Classification Code | Q |
| Position of Line Terminals | Top In - Bottom Out |
| Product Net Depth / Length | 135 mm |
| Package Level 1 Gross Weight | 10 kg |
| Switches Operating Mechanism | Mechanism Between the Poles |
| Declaration of Conformity - CE | 1SCC301227D2706 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Package Level 1 Depth / Length | 310 mm |
| Declaration of Conformity - UKCA | 1SCC301313D0201 |
| Data Sheet, Technical Information | 1SCC301022C0201 |
| Toxic Substances Control Act - TSCA | 1SCC301321D0201 |
| Rated Operational Current DC-21B (Ie) | (1500 V) 1000 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Environmental Product Declaration - EPD | 1SCC301247D0201 |
| Rated Short-Circuit Making Capacity (Icm) | (1500 V DC) 10 kA |
| Improved Resource Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 1000 A |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 -59,09 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | (1500 V DC) 10 kA |
| Positive Opening Operation Torque (Direct Opening Action) | 18 … 30 N·m |
Technical specifications and performance data