| Parameter | Value |
|---|---|
| 33a6131a-e412-4906-9093-8771f82a16ad Norway (NO) | |
| SCIP | 3fba797c-37e6-485d-b2b9-f5c5f3da3053 Finland (FI) |
| ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| UNSPSC | 39122205 |
| eClass | V11.1 : 27371403 |
| Standards | IEC 60947-1, -3 |
| Power Loss | at Rated Operating Conditions per Pole 10 W |
| Handle Type | Pistol handle |
| RoHS Status | Following EU Directive 2011/65/EU |
| Handle Color | Black |
| Neutral Type | No neutral terminal |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| Number of Poles | 3 |
| Simplified SCIP | a896705e-e89d-4fc2-bb45-cfbbc2113123 Germany (DE) |
| Pollution Degree | 3 |
| RoHS Information | 1SCC340075D0201 |
| Country of Origin | Finland (FI) |
| E-Number (Norway) | 1429312 |
| E-Number (Sweden) | 3140234 |
| Product Net Width | 380 mm |
| REACH Declaration | 1SCC340076D0201 |
| Tightening Torque | Main Circuit 44 N·m |
| E-Number (Finland) | 3642416 |
| Enclosure Material | Plastic |
| Product Net Height | 840 mm |
| Product Net Weight | 14.206 kg |
| Package Level 1 EAN | 6417019063331 |
| Cable Entry Position | Top/Bottom |
| Degree of Protection | acc. to IEC 60529 IP65 |
| Customs Tariff Number | 85363090 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 415 mm |
| Cable Outlets Per Side | II-flange / II-flange |
| Minimum Order Quantity | 1 piece |
| Package Level 1 Height | 325 mm |
| Impact Resistance Rating | Housing IK08 |
| Instructions and Manuals | 1SCC340015M0004 |
| Position of PE Terminals | Top In - Bottom Out |
| Recommended Screw Driver | Main Circuit M10 |
| Rated Operational Voltage | Main Circuit 1000 V |
| Mounted Auxiliary Contacts | 2 NO, 1 NC |
| Object Classification Code | Q |
| Position of Line Terminals | Top In - Bottom Out |
| Product Net Depth / Length | 180 mm |
| Package Level 1 Gross Weight | 16.4 kg |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Declaration of Conformity - CE | 1SCC340025D2704 |
| Package Level 1 Depth / Length | 910 mm |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 2 |
| Connecting Capacity Main Circuit | Hole Diameter 10 mm |
| Data Sheet, Technical Information | 1SCC340015C0201 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 220 kW |
| Toxic Substances Control Act - TSCA | 1SCC340095D0201 |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A |
| Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 65 kA |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Rated Conditional Short-Circuit Current (Inc) | 61.5 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA |
Technical specifications and performance data