| Parameter | Value |
|---|---|
| Auxiliary Circuit 24 V DC | |
| ETIM 4 | EC002498 - Accessories for low-voltage switch technology |
| ETIM 5 | EC002498 - Accessories for low-voltage switch technology |
| ETIM 6 | EC002060 - Timer block |
| ETIM 7 | EC002060 - Timer block |
| ETIM 8 | EC002060 - Timer block |
| UNSPSC | 39121500 |
| eClass | V11.0 : 27371308 |
| Standards | IEC/EN 60947-5-1, UL 508, CSA C22-2 No. 14-18 |
| RoHS Status | Following EU Directive 2011/65/EU |
| Feature Name | Feature Value |
| Suitable For | AF09 |
| Terminal Type | Spring Terminals |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| CB Certificate | CB_CN46281 |
| UL Certificate | UL-US-L252354-192-31702102-2 |
| WEEE B2C / B2B | Business To Business |
| ABS Certificate | ABS_20-2060694-PDA |
| CCC Certificate | CCC_2012010303572179 |
| CQC Certificate | CQC2012010303572179 |
| UL Listing Card | UL_E252354 |
| RoHS Information | 2CMT2021-006277 |
| Product Net Width | 43 mm |
| REACH Declaration | 2CMT2021-006202 |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| E-Number (Finland) | 3708073 |
| Product Net Height | 41.3 mm |
| Product Net Weight | 0.065 kg |
| Package Level 1 EAN | 3471523130647 |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Customs Tariff Number | 85389091 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 82 mm |
| Package Level 2 Units | box 80 piece |
| Package Level 2 Width | 254 mm |
| Minimum Order Quantity | 1 piece |
| Package Level 1 Height | 51 mm |
| Package Level 2 Height | 200 mm |
| Ambient Air Temperature | Close to Contactor for Storage -40 ... +80 °C |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Setting time (EF005922) | 0.1 s |
| Instructions and Manuals | 1SBC101026M6801 |
| Resistance to Vibrations | 3g Closed Position & 2g Open Position 5 ... 300 Hz |
| Rated Operational Voltage | Auxiliary Circuit 240 V AC |
| Object Classification Code | K |
| Product Net Depth / Length | 67.7 mm |
| Package Level 1 Gross Weight | 0.065 kg |
| Package Level 2 Gross Weight | 5.2 kg |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 400 V |
| Switching function (EF000189) | Operating delayed |
| Declaration of Conformity - CE | 1SBD250008U1000 |
| Operating principle (EF004139) | Electronic |
| Package Level 1 Depth / Length | 56 mm |
| Package Level 2 Depth / Length | 319 mm |
| Declaration of Conformity - CCC | 2020980303000172 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Declaration of Conformity - UKCA | 1SBD250039U1000 |
| Rated Operational Current AC-15 (Ie) | (24 / 127 V) 3 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 1 A / 24 W |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Maximum Operating Altitude Permissible | Without Derating 2000 m |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 5 A |
| Number of contacts as change-over contact (EF008257) | 0 |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 8 A |
| Number of contacts as normally open contact (EF008256) | 1 |
| Number of contacts as normally closed contact (EF008255) | 1 |
Technical specifications and performance data
Installation and operation guide