| Parameter | Value |
|---|---|
| Feature Name | Feature Value |
| Customs Tariff Number: | 85364900 |
| Minimum Order Quantity: | 1 piece |
| Operate Time: (Dimensions) | Between Coil Energization and NO Contact Closing 8 ... 27 msBetween Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Terminal Type: (Dimensions) | Screw Terminals |
| Coil Consumption: (Dimensions) | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 210 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 18 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 5.5 WHolding at Max. Rated Control Circuit Voltage 50 Hz 18 V·AHolding at Max. Rated Control Circuit Voltage 50 Hz 5.5 WAverage Holding Value 50 / 60 Hz 18 V·AAverage Holding Value 50 / 60 Hz 5.5 WAverage Pull-in Value 50 Hz 180 V·AAverage Pull-in Value 60 Hz 180 V·A |
| CB Certificate: (Environmental) | CB_FR2880_60002378 |
| Climatic Withstand: (Technical) | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| ETIM 4: (Container Information) | EC001079 - Capacitor magnet contactor |
| ETIM 5: (Container Information) | EC001079 - Capacitor magnet contactor |
| ETIM 6: (Container Information) | EC001079 - Capacitor contactor |
| ETIM 7: (Container Information) | EC001079 - Capacitor contactor |
| UL Certificate: (Environmental) | UL_20120830-E312527-10-1 |
| UNSPSC: (Container Information) | 39121529 |
| CCC Certificate: (Environmental) | CCC_2008010304290409 |
| CSA Certificate: (Environmental) | CSA_1033838_LR056745 |
| EAC Certificate: (Environmental) | EAC_RU C-FR ME77 B01010 |
| UL Listing Card: (Environmental) | UL_E312527 |
| E-nummer: (Container Information) | 3228480 |
| GOST Certificate: (Environmental) | GOST_POCCFRME77B07175 |
| RoHS Information: (Environmental) | 1SBD350079R1000 |
| Degree of Protection: (Dimensions) | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Mechanical Durability: (Dimensions) | 10 million |
| Ambient Air Temperature: (Technical) | Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °CNear Contactor for Operation in Free Air (Uc) -40 ... +70 °CClose to Contactor for Storage -60 ... +80 °C |
| Instructions and Manuals: (Ordering) | FPTC407700P0003 |
| Voltage type for actuating (EF008242) | AC |
| Product Net Width: (Popular Downloads) | 70 mm |
| Maximum Breaking Capacity: (Dimensions) | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A |
| Product Net Height: (Popular Downloads) | 110 mm |
| Product Net Weight: (Popular Downloads) | 1.16 kg |
| Rated Operational Voltage: (Dimensions) | Main Circuit 690 V |
| Number of Main Contacts NC: (Dimensions) | 0 |
| Number of Main Contacts NO: (Dimensions) | 3 |
| Instructions and Manuals: (Environmental) | FPTC407700P0003 |
| Environmental Information: (Environmental) | 1SBD250029E1000 |
| Rated Insulation Voltage (Ui): (Dimensions) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V |
| Data Sheet, Technical Information: (Ordering) | 1SBC101140C0203 |
| Number of Auxiliary Contacts NC: (Dimensions) | 0 |
| Number of Auxiliary Contacts NO: (Dimensions) | 0 |
| Connecting Capacity Main Circuit: (Dimensions) | Flexible with Cable End 6 ... 16 mm²Rigid Cable 6 ... 25 mm² |
| Declaration of Conformity - CE: (Environmental) | 1SBD250805U1000 |
| Product Net Depth / Length: (Popular Downloads) | 108 mm |
| Rated reactive power at 400 V, 50 Hz (EF007044) | 33 kvar |
| Rated Control Circuit Voltage (Uc): (Dimensions) | 50 Hz 230 ... 240 V60 Hz 240 ... 260 V |
| Rated control supply voltage AC 50 Hz (EF003978) | 230 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 240 V |
| Connecting Capacity Auxiliary Circuit: (Dimensions) | Flexible with Cable End 0.75 ... 2.5 mm²Rigid Cable 1 ... 4 mm² |
| Maximum Operating Altitude Permissible: (Technical) | 3000 m |
| Object Classification Code: (Container Information) | Q |
| Maximum Mechanical Switching Frequency: (Dimensions) | 3600 cycles per hour |
| Rated Impulse Withstand Voltage (Uimp): (Dimensions) | 8 kV |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of normally open contacts as main contact (EF001374) | 3 |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Package Level 1 EAN: (Certificates and Declarations (Document Number)) | 3471522084880 |
| Package Level 1 Units: (Certificates and Declarations (Document Number)) | 1 piece |
| Package Level 1 Width: (Certificates and Declarations (Document Number)) | 140 mm |
| Package Level 2 Units: (Certificates and Declarations (Document Number)) | 20 piece |
| Package Level 3 Units: (Certificates and Declarations (Document Number)) | 160 piece |
| Package Level 1 Height: (Certificates and Declarations (Document Number)) | 96 mm |
| Connecting terminals (delivered in open position) Main poles: (Dimensions) | M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
| Package Level 1 Gross Weight: (Certificates and Declarations (Document Number)) | 1.16 kg |
| Package Level 2 Gross Weight: (Certificates and Declarations (Document Number)) | 23.2 kg |
| Package Level 1 Depth / Length: (Certificates and Declarations (Document Number)) | 146 mm |
Technical specifications and performance data