| Parameter | Value |
|---|---|
| Main Circuit 50 / 60 Hz | |
| ETIM 6 | EC000066 - Power contactor, AC switching |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| UNSPSC | 39121529 |
| eClass | V11.0 : 27371003 |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1 |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 20 ms |
| Terminal Type | Screw Terminals |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| BV Certificate | BV_2634H24898C0 |
| CB Certificate | CB_SE-113158 |
| UL Certificate | UL-CA-2337656-0_E312527-20231026 |
| WEEE B2C / B2B | Business To Business |
| CQC Certificate | CQC2010010304445623 |
| Coil Consumption | Average Holding Value 50 / 60 Hz 8 V·A |
| RINA Certificate | RINA_ELE334122XG |
| RoHS Information | 2CMT2021-006277 |
| Product Net Width | 45 mm |
| REACH Declaration | 2CMT2021-006202 |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Product Net Height | 86 mm |
| Product Net Weight | 0.357 kg |
| Package Level 1 EAN | 3471523015067 |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Customs Tariff Number | 85364900 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 3 Units | 1080 piece |
| Wire Stripping Length | Control Circuit 10 mm |
| A2L Certificate – UL | 9AKK108469A4886;9AKK108469A4887 |
| Minimum Order Quantity | 1 piece |
| Package Level 1 Height | 47 mm |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 2 hp |
| Instructions and Manuals | 1SBC101027M6801 |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| General Use Rating UL/CSA | (600 V AC) 50 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A |
| Rated Operational Voltage | Main Circuit 690 V |
| Number of Main Contacts NC | 0 |
| Number of Main Contacts NO | 3 |
| Object Classification Code | Q |
| Product Net Depth / Length | 86 mm |
| Package Level 1 Gross Weight | 0.38 kg |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| Declaration of Conformity - CE | 1SBD250024U1000 |
| Package Level 1 Depth / Length | 87 mm |
| Declaration of Conformity - CCC | 2020980304001254 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1.5 ... 10 mm² |
| Declaration of Conformity - UKCA | 1SBD250045U1000 |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Data Sheet, Technical Information | 1SBC100219C0201 |
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Rated Operational Power AC-3 (Pe) | (415 V) 18.5 kW |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
| Rated Control Circuit Voltage (Uc) | 50 Hz 110 V |
| Rated Operational Power AC-3e (Pe) | (415 V) 18.5 kW |
| Rated Operational Power AC-6b (Pe) | (400 / 415 V) 40 °C, 50 / 60 Hz 24 kvar |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 50 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 38 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 38 A |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 14-10 AWG |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
Technical specifications and performance data