| Parameter | Value |
|---|---|
| Customs Tariff Number: | 85364900 |
| Minimum Order Quantity: | 1 piece |
| RoHS Status: (Technical) | No declaration needed |
| Operate Time: (Dimensions) | Between Coil Energization and NO Contact Closing 8 ... 21 msBetween Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Terminal Type: (Dimensions) | Screw Terminals |
| Coil Consumption: (Dimensions) | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 120 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 140 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 3 WHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 50 Hz 3 WAverage Holding Value 50 Hz 12 V·AAverage Holding Value 50 Hz 3 WAverage Holding Value 60 Hz 12 V·AAverage Holding Value 60 Hz 3 WAverage Pull-in Value 50 Hz 120 V·AAverage Pull-in Value 60 Hz 140 V·A |
| CB Certificate: (Environmental) | CB_FR2880_60002378 |
| Climatic Withstand: (Technical) | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| ETIM 4: (Container Information) | EC001079 - Capacitor magnet contactor |
| ETIM 5: (Container Information) | EC001079 - Capacitor magnet contactor |
| ETIM 6: (Container Information) | EC001079 - Capacitor contactor |
| ETIM 7: (Container Information) | EC001079 - Capacitor contactor |
| UL Certificate: (Environmental) | UL_071301E39231 |
| UNSPSC: (Container Information) | 39121529 |
| CCC Certificate: (Environmental) | CCC_2008010304261926 |
| CSA Certificate: (Environmental) | CSA_1033838_LR056745 |
| EAC Certificate: (Environmental) | EAC_RU C-FR ME77 B01010 |
| GOST Certificate: (Environmental) | GOST_POCCFRME77B07175 |
| Rated Frequency (f): (Dimensions) | Supply Circuit 50 HzSupply Circuit 60 Hz |
| RoHS Information: (Environmental) | 1SBC101059D0201 |
| Degree of Protection: (Dimensions) | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Ambient Air Temperature: (Technical) | Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °CNear Contactor for Operation in Free Air (Uc) -40 ... +70 °CClose to Contactor for Storage -60 ... +80 °C |
| Instructions and Manuals: (Ordering) | FPTC407722P0001 |
| Product Net Width: (Popular Downloads) | 54 mm |
| Maximum Breaking Capacity: (Dimensions) | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A |
| Product Net Height: (Popular Downloads) | 90 mm |
| Product Net Weight: (Popular Downloads) | 0.6 kg |
| Rated Operational Voltage: (Dimensions) | Main Circuit 690 V |
| Number of Main Contacts NC: (Dimensions) | 0 |
| Number of Main Contacts NO: (Dimensions) | 3 |
| Instructions and Manuals: (Environmental) | FPTC407722P0001 |
| Environmental Information: (Environmental) | 1SBD250027E1000 |
| Rated Insulation Voltage (Ui): (Dimensions) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V |
| Data Sheet, Technical Information: (Ordering) | 1SBC101140C0203 |
| Number of Auxiliary Contacts NC: (Dimensions) | 0 |
| Number of Auxiliary Contacts NO: (Dimensions) | 1 |
| Connecting Capacity Main Circuit: (Dimensions) | Flexible with Cable End 0.75 ... 4 mm²Rigid Cable 1.5 ... 6 mm² |
| Short-Circuit Protective Devices: (Dimensions) | Auxiliary Circuit - gG Type Fuses 10 AgG Type Fuses 1.5 ... 1.8 A |
| Declaration of Conformity - CE: (Environmental) | 1SBD250805U1000 |
| Product Net Depth / Length: (Popular Downloads) | 93.6 mm |
| Rated Control Circuit Voltage (Uc): (Dimensions) | 50 Hz 190 V60 Hz 220 V |
| Rated Operational Current AC-15 (Ie): (Dimensions) | (220 / 240 V) 4 A(24 / 127 V) 6 A(380 / 440 V) 3 A(500 V) 2 A(690 V) 2 A |
| Rated Operational Current DC-13 (Ie): (Dimensions) | (125 V) 1.1 / 138 A(24 V) 6 / 144 A(250 V) 0.55 / 138 A(48 V) 2.8 / 134 A(72 V) 2 / 144 A |
| Connecting Capacity Auxiliary Circuit: (Dimensions) | Flexible with Cable End 0.75 ... 2.5 mm²Rigid Cable 1 ... 4 mm² |
| Maximum Operating Altitude Permissible: (Technical) | 3000 m |
| Object Classification Code: (Container Information) | Q |
| Maximum Mechanical Switching Frequency: (Dimensions) | 3600 cycles per hour |
| Rated Impulse Withstand Voltage (Uimp): (Dimensions) | 8 kV |
| Conventional Free-air Thermal Current (Ith): (Dimensions) | acc. to IEC 60947-5-1, q = 40 °C 16 A |
| Package Level 1 EAN: (Certificates and Declarations (Document Number)) | 3471522069368 |
| Package Level 1 Units: (Certificates and Declarations (Document Number)) | 1 piece |
| Package Level 1 Width: (Certificates and Declarations (Document Number)) | 101 mm |
| Package Level 2 Units: (Certificates and Declarations (Document Number)) | 63 piece |
| Package Level 3 Units: (Certificates and Declarations (Document Number)) | 576 piece |
| Package Level 1 Height: (Certificates and Declarations (Document Number)) | 61 mm |
| Connecting terminals (delivered in open position) Main poles: (Dimensions) | M 4 (+,-) pozidriv 2 screws with cable clamp |
| Package Level 1 Gross Weight: (Certificates and Declarations (Document Number)) | 0.6 kg |
| Package Level 2 Gross Weight: (Certificates and Declarations (Document Number)) | 37.8 kg |
| Package Level 1 Depth / Length: (Certificates and Declarations (Document Number)) | 115 mm |
Technical specifications and performance data
Installation and operation guide