| Parameter | Value |
|---|---|
| Main Circuit 690 V | |
| ETIM 4 | EC001079 - Capacitor magnet contactor |
| ETIM 5 | EC001079 - Capacitor magnet contactor |
| ETIM 6 | EC001079 - Capacitor contactor |
| ETIM 7 | EC001079 - Capacitor contactor |
| ETIM 8 | EC001079 - Capacitor contactor |
| UNSPSC | 39121529 |
| eClass | V11.0 : 27371006 |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1 |
| RoHS Status | Following EU Directive 2011/65/EU |
| Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Terminal Type | Screw Terminals |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| CB Certificate | CB_CN-58852 |
| UL Certificate | UL-US-L312527-1102-51017991-2 |
| WEEE B2C / B2B | Business To Business |
| CCC Certificate | CCC_2007010304257961 |
| CQC Certificate | CQC2018010304059153 |
| UL Listing Card | UL_E312527 |
| Coil Consumption | Average Holding Value 50 Hz 8 V·A |
| GOST Certificate | GOST_POCCFRME77B07175 |
| RoHS Information | 2CMT2021-006277 |
| Product Net Width | 44 mm |
| REACH Declaration | 2CMT2021-006202 |
| Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Product Net Height | 74 mm |
| Product Net Weight | 0.34 kg |
| Package Level 1 EAN | 3471522254429 |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Customs Tariff Number | 85364900 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 78 mm |
| Package Level 2 Units | box 63 piece |
| Package Level 2 Width | 300 mm |
| Package Level 3 Units | 1220 piece |
| Minimum Order Quantity | 1 piece |
| Package Level 1 Height | 47 mm |
| Package Level 2 Height | 308 mm |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Instructions and Manuals | FPTC407721P0001 |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Number of Main Contacts NC | 0 |
| Number of Main Contacts NO | 3 |
| Object Classification Code | Q |
| Product Net Depth / Length | 74 mm |
| Package Level 1 Gross Weight | 0.34 kg |
| Package Level 2 Gross Weight | 21.42 kg |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V |
| Declaration of Conformity - CE | 1SBD250805U1000 |
| Package Level 1 Depth / Length | 76 mm |
| Package Level 2 Depth / Length | 245 mm |
| Declaration of Conformity - CCC | 2020980304001618 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Connecting Capacity Main Circuit | Flexible with Cable End 1/2x 0.75 ... 2.5 mm² |
| Declaration of Conformity - UKCA | 1SBD250822U1000 |
| Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A |
| Data Sheet, Technical Information | 1SBC101140C0203 |
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Rated Control Circuit Voltage (Uc) | 50 Hz 230 ... 240 V |
| Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 7.5 kvar |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| Connecting Capacity Auxiliary Circuit | Flexible with Cable End 1/2x 0.75 ... 2.5 mm² |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Connecting Capacity Main Circuit UL/CSA | 1/2x 18-10 AWG |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A |
| Connecting Terminals (delivered in open position) Main Poles | M 3.5 (+,-) pozidriv 2 screws with cable clamp |
Technical specifications and performance data
Installation and operation guide