Service time: Monday to Friday 9:00-18:00
1SAM250000R1009 - 1SAM250000R1009 ABB MS116-6.3 Manual Motor Starter
In Stock Hot Product

1SAM250000R1009

1SAM250000R1009 ABB MS116-6.3 Manual Motor Starter

$0.00USD
4832 in stock
Key Specifications
:1SAM200507F0002
ETIM 4:EC000074 - Motor protective circuit-breaker
ETIM 5:EC000074 - Motor protective circuit-breaker
ETIM 6:EC000074 - Motor protection circuit-breaker
Supplier Information
ABB
ABB
Products: 44170
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
1SAM200507F0002
ETIM 4EC000074 - Motor protective circuit-breaker
ETIM 5EC000074 - Motor protective circuit-breaker
ETIM 6EC000074 - Motor protection circuit-breaker
ETIM 7EC000074 - Motor protection circuit-breaker
ETIM 8EC000074 - Motor protection circuit-breaker
UNSPSC39121521
eClassV11.0 : 27370401
StandardsIEC/EN 60947-1
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.8 W
RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Actuator TypeRotary Handle
Setting Range4.0 ... 6.3 A
Terminal TypeScrew Terminals
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
BV Certificate1SAA963000-0204
CB Certificate1SAA963005-2003
GL Certificate1SAA963000-0402
KC Certificate1SAA963000-1501
LR Certificate1SAA963000-0505
UL CertificateE137861-20001218
WEEE B2C / B2BBusiness To Business
ABS Certificate1SAA963000-0104
CQC CertificateCQC2011010307506570
DNV Certificate1SAA963000-0304
EAC Certificate1SAA963000-2701
Number of Poles3
Pollution Degree3
RMRS Certificate1SAA918000-0704
RoHS Information1SAA963006-4502
Dimension Diagram1SAM200422F0001
E-Number (Sweden)3111946
Locked Rotor Amps(200 V AC) Three Phase 37.8 A
Mounting Positionany
Product Net Width45 mm
REACH Declaration1SAA963005-4502
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
DNV GL Certificate1SAA963000-0304
E-Number (Finland)3706009
Product Net Height90 mm
Product Net Weight0.265 kg
I²t Characteristic1SAM200507F0001
Package Level 1 EAN4013614320323
Package Level 2 EAN4013614408694
Rated Frequency (f)Main Circuit 50 Hz
Degree of ProtectionHousing IP20
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Customs Tariff Number85362010
Electrical Durability100000 cycle
Mechanical Durability100000 cycle
Package Level 1 Unitsbox 1 piece
Package Level 1 Width92 mm
Package Level 2 Unitscarton 40 piece
Package Level 2 Width280 mm
Wire Stripping LengthMain Circuit 9 mm
Minimum Order Quantity1 piece
Package Level 1 Height50 mm
Package Level 2 Height210 mm
A2L Certificate – IEC1SAA963000-4601
Ambient Air TemperatureAround the Enclosure 0 ... +40 °C
CAD Dimensional Drawing2CDC001079B0201
End of Life Instructions1SAC200331H0001
Full Load Amps Motor Use(200 V AC) Three Phase 6.3 A
Horsepower Rating UL/CSA(200 V AC) Three Phase 1 Hp
Instructions and Manuals2CDC131011M6802
Recommended Screw DriverPozidriv 2
Resistance to Vibrations5g 3 ... 150 Hz
Tightening Torque UL/CSAMain Circuit 10 in·lb
General Use Rating UL/CSA(600 V AC) 6.3 A
Minimum Mounting DistanceElectrical Conductive Board, Horizontal - Up to 400 V 0 mm
Rated Operational VoltageMain Circuit 690 V AC
Object Classification CodeF
Product Net Depth / Length85.6 mm
Contact Position IndicationON / OFF
Package Level 1 Gross Weight0.28 kg
Package Level 2 Gross Weight11.586 kg
Rated Insulation Voltage (Ui)690 V
Cut-off Current Characteristic1SAM200508F0001
Declaration of Conformity - CE1SAD101100-3401
Package Level 1 Depth / Length95 mm
Package Level 2 Depth / Length395 mm
Rated Operational Current (Ie)6.3 A
Declaration of Conformity - CCC2020980307003705
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Declaration of Conformity - UKCA1SAD201100-3401
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Data Sheet, Technical Information2CDC131025D0201
Instructions and Manuals (Part 2)2CDC131060M0202
Rated Operational Power AC-3 (Pe)(400 V) Three Phase 2.2 kW
Time-Current Characteristic Curve1SAM200505F0009
IDEA Granular Category Code (IGCC)4731 >> Manual Starters
Rated Operational Power AC-3e (Pe)(400 V) Three Phase 2.2 kW
Rated Operational Current AC-3 (Ie)6.3 A
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 18 kA
Toxic Substances Control Act - TSCA2CMT2023-006539
Ambient Air Temperature CompensationYes
Rated Operational Current AC-3e (Ie)6.3 A
Maximum Operating Altitude Permissible2000 m
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-12 AWG
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Conventional Free-air Thermal Current (Ith)Main Circuit 6.3 A
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 75 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)78.8 A

Product Description

MS116-6.3 MOTOR GUARD REG.4.0-6.3A
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top