| Parameter | Value |
|---|---|
| EAN () | 5702424607685 |
| Type () | SonoMeter 40 |
| Media () | Water quality with pH 7 to 9.5 |
| Volume () | 28.25 Liter |
| Net weight () | 12.62 Kilogram |
| qc [m³/h] () | 0.08 m³/h |
| qi [m³/h] () | 0.4 m³/h |
| qp [m³/h] () | 40 m³/h |
| qs [m³/h] () | 80 m³/h |
| Application () | Heating and cooling |
| Battery qty () | 1 |
| Description () | Energy meter for commercial applications |
| Energy unit () | MWh |
| Length [mm] () | 300 mm |
| Display type () | LCD |
| EEE category () | 5 small equipment (any external dimension50 cm) |
| Gross weight () | 12.62 Kilogram |
| Installation () | Return |
| Ambient class () | E2/M1 |
| Approval type () | Type approved and 1st time verified |
| Diameter [mm] () | 80 mm |
| Dynamic range () | 1:100 |
| Product group () | Energy meters |
| Connection size () | DN 80 |
| Connection types () | Flange |
| In scope of WEEE () | Yes |
| SCIP dossier no. () | 0bb8fe81-b381-4f95-92a5-d3d7e2e54c00 |
| Accuracy standard () | Class 2 to EN1434 |
| Approval authority () | MID |
| EU RoHS compliance () | Yes with exemptions |
| Kvs values [m³/h] () | 94.28 m³/h |
| UK RoHS compliance () | Yes |
| Weight per battery () | 19 g |
| IP protection class () | IP65 |
| Supply voltage type () | mains |
| Battery type or Name () | AA Lithium |
| China RoHS compliance () | Out of scope |
| Supply voltage [V] AC () | 230 V |
| Pressure nominal [bar] () | 25 bar |
| Interface module slot 1 () | RS485 ModBus |
| Battery lifetime [Years] () | 15 yr |
| Flow measuring principle () | Ultrasonic |
| Integrated communication () | No integrated communication |
| Temperature sensors type () | Pt 500 |
| Cable insulation material () | Halogen free |
| SCIP dossier product name () | Sono40 |
| 1 Primary battery weight Kg () | 0.019 |
| Log storage duration [Month] () | 36 mo |
| Ambient humidity [% RH] [Max] () | 93 % |
| Media temperature [°C] [Max] () | 130 °C |
| Media temperature [°C] [Min] () | 0 °C |
| 1 Primary battery SUM weight Kg () | 0.019 |
| Ambient temperature [°C] [max] () | 55 °C |
| Ambient temperature [°C] [min] () | 5 °C |
| REACH Candidate List substances () | Lead (CAS no. 7439-92-1) |
| Storage temperature [°C] [Max] () | 35 °C |
| Storage temperature [°C] [Min] () | -25 °C |
| Temperature sensor diameter [mm] () | 5.2 mm |
| Temperature sensors cable length [m] () | 5 m |
| In scope of WEEE and contain batteries () | Yes |
| Approved meteorological range [°C] [Max] () | 180 °C |
| Approved meteorological range [°C] [Min] () | 0 °C |
| Cable length between calculator and flow sensor [m] () | 5 m |
Technical specifications and performance data