| Parameter | Value |
|---|---|
| EAN () | 5702424653378 |
| Type () | EvoFlat MSS |
| Net weight () | 12.5 Kilogram |
| Description () | EvoFlat MSS 1, Fully insulated with Zonevalve and HTC |
| Cover option () | Extra |
| DH pipe size () | Ø18 |
| DHW HEX type () | XB06H-1 26 |
| Gross weight () | 13.7 Kilogram |
| HE pipe size () | Ø18 |
| DHW pipe size () | Ø18 |
| Product group () | Small Stations |
| Cover material () | White-lacquered In wall |
| DHW circulation () | Without |
| Application type () | Direct Heating with mixing & Instantaneous DHW |
| DHW Control type () | Flow/thermostatic |
| HEX heating type () | Brazed |
| DHW capacity [kW] () | 37 kW |
| Station size type () | Type 1 |
| DH connection size () | 3/4" |
| DH connection type () | external thread |
| EU RoHS compliance () | Yes with exemptions |
| HE connection size () | 3/4" |
| HE connection type () | G int. Thread |
| Package depth [mm] () | 600 mm |
| Package width [mm] () | 800 mm |
| DHW connection size () | 3/4" |
| DHW connection type () | G int. Thread |
| DHW controller name () | TPC-M |
| Insulation material () | EPP cover |
| Package height [mm] () | 160 mm |
| Connection direction () | Bottom |
| Heating control type () | Thermostatic + Differential pressure |
| China RoHS compliance () | Out of scope |
| Depth with cover [mm] () | 155 mm |
| Additional information () | EPP Insulated front coverZone valve |
| Heating controller name () | FTC |
| Depth without cover [mm] () | 150 mm |
| EU RoHS exemption clause () | 6(c) |
| Heating circuit - control () | Thermostat |
| Number of households [Min] () | 1 |
| HEX heating gasket material () | EDPM |
| Heating capacity [kW] [Max] () | 15 kW |
| Heating capacity [kW] [Min] () | 10 kW |
| HEX heating brazing material () | Copper |
| Pressure nominal primary [bar] () | 10 bar |
| DCW static pressure [bar] [Min] () | 2 bar |
| REACH Candidate List substances () | Lead (CAS no. 7439-92-1) |
| Differential pressure controller () | Integrated |
| Pressure nominal secondary [bar] () | 10 bar |
| Floor heating circuit - pump type () | Wilo Yonos Para 15/6 |
| Floor heating circuit - pump brand () | Wilo |
| Heat exchanger test pressure [bar] () | 38 bar |
| Supply temperature construction [˚C] () | 95 °C |
| In scope of WEEE and contain batteries () | No |
Technical specifications and performance data
Installation and operation guide