| Parameter | Value |
|---|---|
| LRA | 215 A |
| MCC | 51 A |
| RLA | 36.4 A |
| Phase | 3 |
| Colour | Blue |
| Oil type | POE |
| Oil drain | 1/4'' flare |
| Economizer | No |
| Net weight | 112 Kg |
| Technology | Scroll |
| Description | DSH240-4 (Old) |
| Refrigerant | R410A |
| Shipped oil | Initial oil charge |
| Gross weight | 116.16 Kg |
| Model number | DSH240A4ABB |
| Product type | DSH |
| Relief valve | None |
| Diameter [mm] | 318 mm |
| Gauge port HP | None |
| Gauge port LP | Schrader |
| Oil reference | 160SZ |
| Segment usage | Air conditioning |
| Drawing number | 8556089g |
| Frequency [Hz] | 50/60 |
| Glass mounting | Threaded |
| Oil charge [L] | 6.7 L |
| Packing format | Industrial pack |
| Shipped module | Electronic protection module mounted in terminal box |
| Viscosity [cP] | 32 cP |
| Brand technique | Scroll compressor |
| Connection type | Brazed |
| Capacity control | Fixed speed |
| Fitting standard | ODF |
| Motor protection | Electronic protection module, 110/240 V |
| Oil equalization | 2-1/4'' Rotolock |
| Packing quantity | 6 |
| Type designation | Compressor |
| Approval standard | CEUL |
| Glass torque [Nm] | 50 N-m |
| Power connections | Screw 4.8 mm |
| Torque earth [Nm] | 2 N-m |
| Torque power [Nm] | 3 N-m |
| Total height [mm] | 683 mm |
| Configuration code | Single |
| Swept volume [cm3] | 227.6 cm3 |
| IP protection class | IP54 (with cable gland) |
| Test HP [bar] [Max] | 48.7 bar |
| Test LP [bar] [Max] | 34.3 bar |
| Mounting torque [Nm] | 21 N-m |
| Shipped instructions | Installation instructions |
| Test dif [bar] [Max] | 37 bar |
| Reverse rotation protection | Electronic module |
| Suction connection size [in] | 1.625 in |
| Refrigerant charge [kg] [Max] | 15 kg |
| Discharge connection size [in] | 1.125 in |
| Rotational speed at 50Hz [rpm] | 2900 rpm |
| Rotational speed at 60Hz [rpm] | 3500 rpm |
| Suction connection height [mm] | 331 mm |
| Number of starts per hour [Max] | 12 |
| Discharge connection height [mm] | 648 mm |
| Nominal cooling capacity at 50Hz | 53 kW |
| Nominal cooling capacity at 60Hz | 72.3 kW |
| Compressor power supply [V/Ph/Hz] | 400/3/50 460/3/60 |
| Suction connection pipe size [in] | 1.625 in |
| Nominal cooling capacity 60 kBTU/h | 246.76 KBtu/h |
| Discharge connection pipe size [in] | 1.125 in |
| Low value of voltage range at 50Hz [V] | 342 V |
| Low value of voltage range at 60Hz [V] | 414 V |
| High value of voltage range at 50Hz [V] | 440 V |
| High value of voltage range at 60Hz [V] | 506 V |
| Low value of nominal voltage at 50Hz [V] | 380 V |
| Low value of nominal voltage at 60Hz [V] | 460 V |
| High value of nominal voltage at 50Hz [V] | 400 V |
| High value of nominal voltage at 60Hz [V] | 460 V |
| Winding resistance for three-phase compressors with identical windings [Ohm] | 0.616 Ohm |