| Parameter | Value |
|---|---|
| MCC | 22.3 A |
| RLA | 15.9 A |
| Region | Africa; Europe; Middle East |
| DLLP_CU | 4 |
| K limit | 1052 |
| Version | A02 |
| Type Code | Optyma™ |
| Net weight | 149.50 Kg |
| Width [mm] | 900 |
| Length [mm] | 900 |
| Refrigerant | R404A; R507 |
| Applications | LBP |
| Gross weight | 149.50 Kg |
| Model number | OP-LCHC215NTA02E |
| • Receiver | 8168183 |
| Segment usage | Low Back Pressure |
| • Condenser | 118U8008 |
| Condenser type | J4 |
| Number of fans | 1 |
| • Compressor | 120F0013 |
| Electrical code | E |
| Compressor model | NTZ215-4 |
| Type designation | Condensing Units |
| Voltage 50Hz [V] | 400 |
| • Fan assembly | 118U8023 |
| Receiver approval | CE |
| Total height [mm] | 708 |
| • Suction valve | 7968018 |
| Approval standards | CE - LVD |
| Fan blade size [mm] | 500 |
| No. of phases (fan) | 1 |
| • Discharge valve | 7968015 |
| • Crankcase heater | 7773108 |
| Fan current @ 50Hz [A] | 3 |
| Fan current @ 60Hz [A] | 3.92 |
| Voltage 50Hz [V] [Max] | 400 |
| Air flow @ 50Hz [m³/h] | 6000 |
| • Dual pressure switch | 060-539766 |
| • Receiver Description | 14L |
| • Condenser Description | J4 |
| Fan power supply [V/Ph/Hz] | 230/1/50 |
| No. of phases (compressor) | 3 |
| Sound power @ 50Hz [db(A)] | 86 |
| • Compressor Description | NTZ215-4 |
| • Compressor single pack | 120F0006 |
| Liquid line connection [in] | 5/8 |
| Suction connection size [in] | 1 1/8 |
| • Fan assembly Description | D500 230/1/50-60 |
| • Suction valve Description | V02 |
| • Discharge valve Description | V04 |
| Fan power consumption @ 50Hz [W] | 680 |
| Fan power consumption @ 60Hz [W] | 890 |
| • Crankcase heater Description | Belt type crankcase heater, 75 W, 230 V, CE mark, UL |
| Compressor power supply [V/Ph/Hz] | 400/3/50 |
| Fan voltage @ 50Hz (max) [V] [Max] | 230 |
| Fan voltage @ 50Hz (max) [V] [Min] | 230 |
| • Dual pressure switch Description | KP 17 WB |
| • Compressor single pack Description | NTZ215-4 |
Technical specifications and performance data
Installation and operation guide