| Parameter | Value |
|---|---|
| EAN () | 5702422186977 |
| Coil () | No |
| Type () | AKVA 15-1 |
| Volume () | 6.248 Liter |
| Approval () | EACLLC CDC TYSK |
| Function () | NC |
| Direction () | Straightway |
| Net weight () | 1.937 Kg |
| Serviceable () | Electric valve spare parts |
| Gross weight () | 2.125 Kg |
| MinODP [bar] () | 0.45 bar |
| MinODP [psi] () | 6.52 psi |
| Refrigerants () | R744R717 |
| Body material () | Steel |
| MOPD[bar/psi] () | 22 bar |
| Product group () | Expansion valves |
| Packing format () | Single pack |
| Inlet size [in] () | 3/4 in |
| Kv value [m³/h] () | 0.25 m³/h |
| Outlet size [in] () | 3/4 in |
| Type designation () | Electric expansion valve |
| Orifice size [mm] () | 5.6 mm |
| Working principle () | PWM |
| Cv value [gal/min] () | 0.289 gal/min |
| EU RoHS compliance () | Yes with exemptions |
| MaxOPD[bar] 10W AC () | 22 bar |
| MaxOPD[psi] 10W AC () | 318 psi |
| Parts Program name () | AKVA |
| Ambient temperature () | -40 - 50 °C |
| Product accessories () | FlangesElectric valve accessories |
| Actuator system [mm] () | 13.5 mm |
| Inlet connection type () | Flange connection |
| Outlet connection type () | Flange connection |
| Manual operation option () | No |
| Flow direction indicator () | Embossed 1-way arrow |
| Product Name Description () | Electric expansion valve |
| Rated capacity R717 [kW] () | 125 kW |
| Rated cap. conditions [SI] () | tcond=32 °Ctliq=28 °Ctevap=5 |
| Max. Working Pressure [bar] () | 42 bar |
| Quantity per packing format () | 1 pc |
| Rated cap. conditions [IMP] () | tcond=90 °Ftliq=82 °Ftevap=4 |
| Max. Working Pressure [psig] () | 610 psig |
| Compatible Danfoss controllers () | EKC 315AEKE 347 |
| REACH Candidate List substances () | No |
| Medium temperature range [°C] [max] () | 60 °C |
| Medium temperature range [°C] [min] () | -40 °C |
| Medium temperature range [°F] [max] () | 140 °F |
| Medium temperature range [°F] [min] () | -40 °F |
| Ambient temperature range [°F] [max] () | 120 °F |
| Ambient temperature range [°F] [min] () | -40 °F |
| In scope of WEEE and contain batteries () | No |
Technical specifications and performance data