| Parameter | Value |
|---|---|
| EAN | 5702428322232 |
| Approval | EACLLC CDC TYSK |
| Net weight | 0.25 Kg |
| Serviceable | TXV spare parts |
| Gross weight | 0.3 Kg |
| Orifice size | 11 |
| Product name | Orifice for expansion valve |
| Product type | Orifice |
| Refrigerants | R134aR404A/R507R407CR22R407AR407F |
| Product Group | Expansion valves |
| Packing format | Multi pack |
| Valve operation | Solenoid operated |
| Type designation | Orifice |
| Used for product | TE 55 |
| Parts Program name | TE 55 |
| Product accessories | TXV accessories |
| Product family name | TE 5 - 55 |
| Balanced port [Yes/No] | Yes |
| System line application | Liquid line |
| Quantity per packing format | 8 pc |
| Rated cap. R22, Range B [TR] | 25.3 tons |
| Rated cap. R22, Range B [kW] | 89 kW |
| Rated cap. R22, Range N [TR] | 52 tons |
| Rated cap. R22, Range N [kW] | 183 kW |
| Rated cap. R507, Range B [TR] | 16.2 tons |
| Rated cap. R507, Range B [kW] | 56.7 kW |
| Rated cap. R507, Range N [TR] | 39 tons |
| Rated cap. R507, Range N [kW] | 137 kW |
| Rated cap. cond. Range N [SI] | tconc=38 °Ctevap=4.4 °Ctliq=37 °C |
| Rated cap. R134a, Range N [TR] | 34 tons |
| Rated cap. R134a, Range N [kW] | 120 kW |
| Rated cap. R404A, Range B [TR] | 16.2 tons |
| Rated cap. R404A, Range B [kW] | 56.7 kW |
| Rated cap. R404A, Range N [TR] | 39 tons |
| Rated cap. R404A, Range N [kW] | 137 kW |
| Rated cap. R407A, Range N [TR] | 52 tons |
| Rated cap. R407A, Range N [kW] | 183 kW |
| Rated cap. R407C, Range N [TR] | 50 tons |
| Rated cap. R407C, Range N [kW] | 176 kW |
| Rated cap. R407F, Range N [TR] | 53 tons |
| Rated cap. R407F, Range N [kW] | 186 kW |
| Rated cap. cond. Range N [IMP] | tcond=100 °Ftevap=40 °Ftliq=98 °F |
Technical specifications and performance data
Installation and operation guide